23
If the memorization condition is forced cooling
mode, the unit will run in cooling mode for 30
minutes and turn to auto mode as 24°C(75.2°F)
setting temp.
If AC is off before power off and AC is required
to start up now, the compressor will have 1
minute delay when power on. Other conditions,
the compressor will have 3 minutes delay when
restarts.
8.4.8 8°C Heating(optional)
When the compressor is running, the indoor fan
motor will run without anti-cold air function.
When the compressor is off, the indoor fan
motor is off .