For other models:
8.4.3.5 Evaporator coil temperature protection
----T2> TEH2
℃
, the compressor running frequency decreases to the lower level and runs for 20s.
When the frequency decreases to F2 and the T2 is still over TEH2
℃
for 3 minutes, the compressor
will stop.
----T2<48
℃
or T2 stays in 48
℃
~ TEH2
℃
for 6 minutes, the frequency will not be limited by T2.
----T2>60
℃
, the compressor will stop and restart when T2<48
℃
.
While TEH2=55
℃
for MS9A-9HRDN1-BQ0W, MS9A-24HRDN1-MP0W, MS9A-24HRDN1-MS0W;
TEH2=53
℃
for other models.
8.4.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30
℃
.
In auto mode, the machine will choose cooling, heating or fan-only mode according to
Δ
T (
Δ
T =T1-Ts).
Δ
T=T1-Ts Running
mode
Δ
T
>
1
℃
Cooling
-1<
Δ
T
≤
1
℃
Fan-only
Δ
T
≤
-1
℃
Heating