Air Conditioner Service Manual
6
In the
“Feel”
mode, when the controller receives the up or down signal of temperature, the set
temperature can adjust by 1
℃
upper or lower. The biggest you can adjust by 2
℃
upper or lower.
3. “COOLING” Mode Operation
(1) Compressor frequency control
According to difference room temperature and set temperature (
δt = RT-ST
), running frequency
of compressor is controlled by electronic controller. When room temperature is much higher than
set temperature, the compressor will start at a high frequency, and as room temperature goes
down, the compressor running frequency will go down. When room temperature is lower than set
temperature,
the c
ompressor will run at very low frequency. In general, unit will change its running
frequency according to
δt
to make room temperature closing to set temperature.
(2) Outdoor temperature affects running frequency of the compressor
Outdoor temperature affect
compressor’s
running frequency. Difference inlet temperature of
outdoor unit is adapted by difference compressor running frequency. While outdoor temperature is
about 30
℃
, the compressor will run in high frequency.
If unit run in
“cooling”
mode and outdoor temperature is less than -2
℃
,
the
controller will shut
down compressor and show error code, while the ambient temperature is over 1
℃
,
the compressor
will run automatically
.
(3) Auto fan control in cooling mode
In cooling mode (include cooling in
“
F
eel”
mode), fan speed is determined by
δt
, as the
following diagram:
4.“DRY” Mode Operation
(1) The system for DRY operation used the same refrigerant circle as the cooling one.
(2) When the system operates in DRY mode, at first it operates in cooling mode, the set
temperature (
ST
) is
“RT
-2
℃
”
. After that, t he system will operate in cooling mode with
lowest fan speed. During the course of this operation, you can
’
t use remote controller to adjust
the fan speed but you can control the vane direction.
(3) In the dry mode, when RT
≤
12
℃
, the compressor will stop and operates again at RT
≥
14
℃
.
5. “HEATING” Mode Operation (available for Heat Pump only)
(1) Frequency control
Same as the frequency control in cooing mode, the running frequency of compressor is
controlled by controller. Unit change its running frequency according to
δt
to make the room
temperature closing to the set temperature.
(2) Indoor fan motor control
1) Cold Air Prevention C
ontrol
The function is intended to prevent cold air from being discharged when heating mode
selected or while in defrosting.
The indoor fan speed will be controlled as following.
RT-ST
℃
4.0
3.0
1.5
1.0
δt
come down
δt
come up
High fan
Min fan
Low fan
Summary of Contents for WT009GLFI22HLD
Page 3: ......
Page 5: ......
Page 13: ......
Page 14: ......
Page 15: ......
Page 19: ......
Page 20: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 35: ......
Page 36: ......
Page 37: ......