Sheet metal ductwork run in unconditioned spaces 

must be insulated and covered with a vapor barrier. 

Fibrous ductwork may be used if constructed and 

installed in accordance with SMACNA Construction 

Standard on Fibrous Glass Ducts. Ductwork must 

comply with National Fire Protection Association as 

tested by U/L Standard 181 for Class l Air Ducts. 

Check local codes for requirements on ductwork and 

insulation.

The duct system must be designed within the range of 

external static pressure the unit is designed to operate 

against. It is important that the system airflow is 

adequate. Ensure that the supply and return duct 

work, grills, special filters, accessories, etc, are 

accounted for in total resistance calculations.

Installation and Maintenance

4. Refrigerant Pipe

Use refrigerant spec. according to the outdoor unit 

nameplate. When carrying out the leakage check 

and test, do not mix in any oxygen, acetylene, or 

any sort of flammable/reactive gas, as these gases 

may result in explosion. It is recommended to use 

nitrogen to perform these procedures.

4.1 Pipe Material

(1) Prepare the copper pipe on-site.

(2) Choose dust-free, non-humid, clean copper pipe.

Before installing the pipe, use nitrogen or dry air

to blow away any dust or impurities on the pipe.

(3) Select the copper piping according to outdoor

manual.

4.2 Piping Connection

(1) The connection positions of the pipe are shown in

Fig. 4.1.

DANGER

(Unit: in.)

Fig. 4.1

.

 Connection 

P

ositions of the 

P

ip

ing

Refer to the "Outdoor Unit Installation Instructions" 

for details on piping size selection, piping 

installation, and charging information.

The coil is shipped filled with Nitrogen. Evacuate 

the system before charging with refrigerant. 

Install refrigerant lines so that it does not block 

service access to the front of the unit.

Nitrogen should flow through the refrigerant lines 

while brazing.

Use a wet rag or an approved heat paste to protect 

the TXV sensing bulb during the brazing process.

5. Drain Piping

The indoor units has a field supplied with primary 

and secondary 3/4-in. NPT drain connections. 

When making drain fitting connections to the drain 

pan, use a thin layer of Teflon paste, silicone, or 

Teflon tape and install. Hand-tighten afterwards.

When making drain-fitting connections to drain pan, 

do not over-tighten.

All horizontal drain pipes must be pitched downward 

away from the unit at a minimum of 1/8" per foot to 

provide problem-free drainage.

(Unit: in.)

6
6

To Approved Drain

Do not operate unit without 

condensate drain trap.

Condensate Drain Trap

Do not over-tighten 

drain fitting. Unit must 

be slightly pitched 

toward drain connection.

8

Do not connect the drain pipes directly to sewage pipes, to 

avoid ammonia odors. The ammonia in the sewage can enter 

the indoor unit through the drain pipes and corrode the heat 

exchanger. 

Do not twist or bend the drain hose, as excessive force is 

applied during twisting or bending and may also cause 

leakage.

The drain line should be insulated where necessary, to 

prevent sweating and damage due to condensate forming on 

the outside surface of the pipe.

Test condensate drain pan and drain pipe after installation is 

complete. Keep the case horizontal (horizontal left or 

horizontal right) to ensure a smooth drainage, or incline the 

case 0.5° to the drainage hole, making it the lowest point for 

draining. Pour water into drain pan, enough to fill drain trap 

and line. Check to make sure drain pan is draining completely, 

no leaks are found in drain pipe fittings, and water is draining 

from the termination of the primary drain pipe.

NOTES:

If unit is located in or above a living space where damage may 

result from condensate overflow, a field-supplied, external 

condensate pan should be installed underneath the entire unit, 

and a secondary condensate line (with appropriate trap) should 

be run from the unit into the pan. Any condensate in this external 

condensate pan should be drained to a designated place. The 

owner of the structure must be informed that when condensate 

flows from the secondary drain or external condensate pan, the 

unit requires servicing, or water damage will occur. Install traps in 

the condensate lines as close to the coil as possible.

1-5/8

3-1/4

1-3/8

2-7/8

-1

1/

2

-1

1/

2

H

: 1

4-

5/

8(

24

K

/3

6K

)

9-1

3/

8(

48

K

/6

0K

-1

1/

4

33-7/

Fig. 4.1.

Summary of Contents for DR024GHFD18HT2

Page 1: ...s Air Conditioner Please read this manual carefully before installing or operating your new air conditioning system Be sure to save this manual for future reference HIGH EFFICENCY AIR HANDLER Models DR024GHFD18HT2 DR036GHFD18HT2 DR048GHFD18HT2 DR060GHFD18HT2 R 410A REFRIGERANT 208 230V 1 Phase 60Hz 18 SEER ...

Page 2: ...This page intentionally left blank ...

Page 3: ...k 5 2 2 Installation Location 6 2 3 Installation 6 2 4 Air Duct 6 4 Refrigerant Pipe 8 4 1 Pipe Material 8 4 2 Piping Connection 8 5 Drain Piping 8 6 Electrical Wiring 9 6 1 Electrical Installation 9 6 2 Change of Static Pressure 10 7 Test Run 10 8 TXV Replacement Information 11 9 Electric Heat Kit Selection Table 11 Filter Cleaning 4 3 Special Instructions for Down flow Conversion 7 ...

Page 4: ... done by a qualified electrician All wiring operations must be conducted according to the local electrical codes It is strongly advised to consider the capacity of the electric current of the available electrical meter and socket before installation The power source of where this product is installed should have an independent leakage protection device An electric current over load protection devi...

Page 5: ...ulation Carbon Monoxide CO Formaldehyde Benzene More details are available at the websites for OSHA Occupational Safety and Health Administration at www osha gov and the State of California s OEHHA Office of Environmental Health Hazard Assessment at www oehha org Consumer education is important since the chemicals and substances on the list are found in our daily lives Most consumers are aware tha...

Page 6: ... Low Voltage Connection for 24V 3 Circuit Breaker Switch Optional 4 Refrigerant Pipe Gas 5 Refrigerant Pipe Liquid 6 Air Inlet 7 Auxiliary Drainage Hole 8 Drainage Hole 9 Auxiliary Drainage Hole 10 High Voltage Connection 11 High Voltage Connection 12 Air Outlet 13 Auxiliary Heater Optional 14 Electronic Control Box 15 Fan Volute 16 Evaporator 17 Drainage Pan 18 Filter Cover 13 14 15 16 17 18 1 2 ...

Page 7: ... and panels and ensure that there is sufficient ventilation Sounds from Moving Parts When starting or stopping the system a sound might be made However this is likely due to thermal deformation of plastic parts If so it is not abnormal Steam from Outdoor Heat Exchanger During the defrosting operation ice on the outdoor heat exchanger melts resulting in steam Dew on Air Panel When the cooling opera...

Page 8: ...nitrogen escapes otherwise it can indicate an evaporator leak When installing or relocating the system be sure to keep the refrigerant circuit free from air Air in the refrigerant circuit may cause an abnormal pressure rise or rupture resulting in injury or damage If any refrigerant leakage occurs during the installation work ventilate the room liberally After all installation is completed ensure ...

Page 9: ... and humid place it is recommended to insulate the cabinet exterior and to use auxiliary drain pans If installed above a finished living space an auxiliary drain pan as required by many building codes must be installed under the entire unit and its condensate drain line must be routed to a location such that the user will see the condensate discharge 6 The upright installation method is selected b...

Page 10: ... fan 4 Pull the fan out of the guide rail and place it on a flat surface for easy operation 5 Take out the sponge in the accessories bag and paste the sponge to the surface of the fan according to the scheme shown in the right picture 6 Reinstall the fan back to the device by following the reverse steps of steps 4 3 and 2 for the inverted installation connect the grounding wire and power cable cor...

Page 11: ... in NPT drain connections When making drain fitting connections to the drain pan use a thin layer of Teflon paste silicone or Teflon tape and install Hand tighten afterwards When making drain fitting connections to drain pan do not over tighten All horizontal drain pipes must be pitched downward away from the unit at a minimum of 1 8 per foot to provide problem free drainage Unit in 6 6 To Approve...

Page 12: ...er details Wiring Diagram 9 L1 L2 PE Power supply Power supply Thermostat Indoor unit Outdoor unit Power terminal panel L1 L2 W1 B C R Y G G R C C B Y W SI W1 SI If the matching outdoor condensing unit does not have an S1 terminal then ignore the S1 to S1 connection Electrical data NOTE 1 1 Do not connect dashed line when electric heater is not used 2 Wiring must be performed according to wiring d...

Page 13: ...NOTE Symbol indicates the position of the dip switch Symbol indicates any position of ON or OFF Blower Speed Tap Static Pressure W C kPa 24K Static Pressure W C kPa 36K Static Pressure W C kPa 48K 60K 1 Follow local codes and regulations when selecting field wires All the above are the minimum wire sizes 2 When transmission cable length is longer than 262ft 80m a thicker wire size should be select...

Page 14: ...just the TXV superheat to 6 10 When the unit has operated for another 20 minutes examine whether the superheat is appropriate and record the figures afterwards available unavailable NOTE The heat kit is an optional part and it must be connected to the power supply separately It is recommended that electric heater kit should be installed in low temperature area or when long piping is used Check if ...

Page 15: ...This page intentionally left blank ...

Page 16: ...er Davis HVAC International Inc Parker Davis HVAC International Inc 3250 NW 107 Avenue Doral FL 33172 USA Tel 305 513 4488 Fax 305 513 4499 E mail info pdhvac com Website www pdhvac com Pioneer product line parts and supplies are available online for convenient ordering at www highseer com www pioneerminisplit com Scan the below code to visit our support page where you can find more installation m...

Reviews: