Function Description
Operating Manual PSSu E AI SHT2
1003113-EN-02
11
4
Function Description
4.1
Block diagram
13 23
C-Rail
16 26
(C-Rail)
1 4
1 1
2 1
2 4
1 2
2 2
R 1
R 2
4.2
Module features
4.2.1
Functions
The electronic module E AI SHT2 contains two shunts for scaling an input current I
I0
(con-
nection I0). The two current outputs I
O0
(connection O0+) and I
O1
(connection O1+) are eval-
uated by analogue current inputs.
Scaling is applied during evaluation via an analogue input module with an input resistance
of 115 Ohm, (e.g. PSSu E F AI I)
}
Scaling factor with resistance R
1
+ R
2
= 10,150 Ohm (connections O0+/O0-):
I
O0
: I
I0
= 1:10
}
Scaling factor with resistance R
2
= 6,750 Ohm (connections O1+/O1-):
I
O1
: I
I0
= 1:20
The maximum output variable error at 25 °C is:
}
When two analogue input modules are connected (e.g. PSSu E F AI I) 1,0 %
}