Technical Details
Operating Manual PSS u2 EF 2DO R 8A
1003625-EN-03
| 26
9
Technical Details
General
Certifications
CE, TÜV, cULus Listed
Application range
Failsafe
Module's device code
404Eh
Number of FS output bits
2
Number of FS status bits
2
Electrical data
Supply voltage
Potential isolation
yes
Internal supply voltage (module supply)
Module's power consumption
0,45 W
Periphery's supply voltage (periphery supply)
Voltage range
16,8 - 30 V
Module's current consumption with no load
40 mA
Module's power consumption with no load
1,2 W
Max. power dissipation of module
2,6 W
Permitted loads
inductive, resistive
Relay outputs
Number of relay outputs
2
Utilisation category
In accordance with the standard
EN 60947-4-1
Utilisation category of safety contacts
AC1 at
250 V
Min. current
5 mA
Max. current
10 A
Max. power
2300 VA
DC1 at
24 V
Min. current
5 mA
Max. current
10 A
Max. power
240 W
Utilisation category
In accordance with the standard
EN 60947-5-1
Utilisation category of safety contacts
AC15 at
230 V
Max. current
3 A
DC13 (6 cycles/min) at
24 V
Max. current
5 A
Utilisation category in accordance with UL
Voltage
250 V AC G.U. (same polarity)
With current
6 A
Voltage
24 V DC G. U.
With current
6 A
Pilot Duty