PNOZ mmc3p
Operating Manual1002423EN02
Configurable Control System PNOZmulti
Page 1: ...PNOZ mmc3p Operating Manual 1002423 EN 02 Configurable Control System PNOZmulti ...
Page 2: ...o KG Copies may be made for internal purposes Suggestions and comments for improving this documentation will be gratefully received Pilz PIT PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries SD means Secure Digital ...
Page 3: ... 1 Operation 10 4 2 Input and output data 10 4 3 Assigning the inputs outputs in the PNOZmulti Configurator to the PROFIBUS DP inputs outputs 11 4 4 Block diagram 11 Section 5 Installation 12 5 1 General installation guidelines 12 5 2 Connect the base unit and expansion modules 12 5 3 Dimensions 13 Section 6 Commissioning 14 6 1 General wiring guidelines 14 6 2 Connecting the supply voltage 14 6 3...
Page 4: ...follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures that can be taken WARNING This warning must be heeded It warns of a hazardous situation that could lead to serious injury and death and indicates preventive measures that can be taken CAUTION This refers to a hazard that can lead ...
Page 5: ...Introduction Operating Manual PNOZ mmc3p 1002423 EN 02 5 INFORMATION This gives advice on applications and provides information on special fea tures ...
Page 6: ...rrors 24 virtual inputs and outputs on the control system PNOZmulti can be defined in the PNOZmulti Configurator for communication with the fieldbus PROFIBUS DP The num ber of inputs and outputs can be extended to 128 Please note that when the extended inputs and outputs 24 127 are used they have different properties see document en titled Communication Interfaces Max 1 PNOZ mmc3p can be connected...
Page 7: ...verview Operating Manual PNOZ mmc3p 1002423 EN 02 7 2 3 Front view Legend 0 V 24 V Supply connections X1 PROFIBUS DP interface female 9 pin D Sub connector Functional earth LED Power Online Offline Fault ...
Page 8: ...cted The configurable control system PNOZmulti is used for the safety related interruption of safety circuits and is designed for use in E STOP equipment Safety circuits in accordance with VDE 0113 Part 1 and EN 60204 1 The expansion module may not be used for safety related functions Intended use includes making the electrical installation EMC compliant The product is de signed for use in an indu...
Page 9: ...he manual Operating personnel are not suitably qualified Any type of modification has been made e g exchanging components on the PCB boards soldering work etc 3 3 3 Disposal In safety related applications please comply with the mission time tM in the safety re lated characteristic data When decommissioning please comply with local regulations regarding the disposal of electronic devices e g Electr...
Page 10: ...ator s online help INFORMATION The GSD file is available on the Internet at www pilz de 4 2 Input and output data The data is structured as follows Input range The inputs are defined in the master and transferred to the PNOZmulti Each input has a number e g input bit 4 of byte 1 has the number i12 Output range The outputs are defined in the PNOZmulti Configurator Each output that is used is given ...
Page 11: ...I8 I15 I16 I23 Input data PROFIBUS DP Byte 0 Bit 0 7 Byte 1 Bit 0 7 Byte 2 Bit 0 7 Virtual outputs on PNOZmulti Configurator O0 O7 O8 O15 O16 O23 Output data PROFIBUS DP Byte 0 Bit 0 7 Byte 1 Bit 0 7 Byte 2 Bit 0 7 The number of virtual inputs and outputs can be extended to 128 see document Commu nication Interfaces in the section entitled Fieldbus modules 4 4 Block diagram Base unit PROFIBUS DP 2...
Page 12: ...To comply with EMC requirements the mounting rail must have a low impedance con nection to the control cabinet housing The ambient temperature of the PNOZmulti units in the control cabinet must not exceed the figure stated in the technical details otherwise air conditioning will be required CAUTION Damage due to electrostatic discharge Electrostatic discharge can damage components Ensure against d...
Page 13: ...Installation Operating Manual PNOZ mmc3p 1002423 EN 02 13 5 3 Dimensions 115 0 4 53 ...
Page 14: ...tive sep aration 6 2 Connecting the supply voltage Connect the supply voltage to the fieldbus module Terminal 24 V 24 V DC Terminal 0 V 0 V 6 3 PROFIBUS DP interface It is possible to define which outputs on the control system will communicate with PROFIBUS DP The connection to PROFIBUS DP is made via a female 9 pin D Sub con nector in accordance with the guidelines of the PROFIBUS User Group PNO ...
Page 15: ...address 6 in the example Station address 36 is set in the diagrams as an example 6 5 Download modified project to the control system PNOZmulti As soon as an additional expansion module has been connected to the system the project must be amended using the PNOZmulti Configurator Proceed as described in the operat ing instructions for the base unit NOTICE For the commissioning and after every progra...
Page 16: ...Commissioning Operating Manual PNOZ mmc3p 1002423 EN 02 16 6 6 Connection example PROFIBUS DP Master PROFIBUS DP Slave 1 PROFIBUS DP Slave 2 PROFIBUS DP Slave 3 PROFIBUS DP Slave n PNOZ mmc3p PROFIBUS ...
Page 17: ...3p does not receive a configuration from the base unit for a period of 30 s the expansion module PNOZ mmc3p connects to PROFIBUS DP and ONLINE status is displayed on PROFIBUS DP The error message External Error is sent to the Master 7 1 Messages Legend LED on LED flashes LED off LED Meaning POWER Supply voltage is present Supply voltage is not present ONLINE PNOZ mmc3p Online data exchange is poss...
Page 18: ... during initialisation of the PNOZ mmc3p does not match the configuration Remedy Ensure that the right GSD file has been used 2 Hz Configuration error length contents of configuration data during initialisation of the PNOZ mmc3p does not match the configuration Remedy Ensure that the right GSD file has been used 4 Hz Error when initialising PROFIBUS DP No fault ...
Page 19: ...mes 772032 Supply interruption before de energisation 20 ms Environmental data 772032 Ambient temperature In accordance with the standard EN 60068 2 14 Temperature range 0 60 C Forced convection in control cabinet off 55 C Storage temperature In accordance with the standard EN 60068 2 1 2 Temperature range 25 70 C Climatic suitability In accordance with the standard EN 60068 2 30 EN 60068 2 78 Hum...
Page 20: ... rail 35 x 7 5 EN 50022 Recess width 27 mm Material Bottom PC Front PC Top PC Conductor cross section with screw terminals 1 core flexible 0 25 2 50 mm 24 12 AWG 2 core with the same cross section flexible with crimp connectors no plastic sleeve 0 20 1 50 mm 24 16 AWG 2 core with the same cross section flexible without crimp connectors or with TWIN crimp connectors 0 20 1 50 mm 24 16 AWG Torque se...
Page 21: ...der no PNOZ mm0 xp connector left Jumper yellow black to connect the modules 1 piece 779 260 Connection terminals Product type Features Order no Spring terminals PNOZ mmcxp 1 pc Spring loaded terminals 1 pieces 783 542 Spring terminals PNOZ mmcxp 10 pcs Spring loaded terminals 10 pieces 783 543 Screw terminals PNOZ mmcxp 1 pc Screw terminals 1 piece 793 542 Screw terminals PNOZ mmcxp 10 pcs Screw ...
Page 22: ...imo PMCprotego PMCtendo PMD PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document depending on the status at the time of publication and the scope of the equipment We accept no responsibility for the va...