PNOZ XV2.1
Operating Manual PNOZ XV2.1
20690-EN-08
| 10
Wiring
Please note:
}
" must be followed.
}
Delivery status of units with screw terminals: Link between S11-S12 (dual-channel input
circuit) and link between Y39-Y40 (reset circuit)
}
Outputs 13-14, 23-24 are instantaneous safety contacts, outputs 37-38, 47-48 are delay-
on de-energisation safety contacts.
}
Do not connect undesignated terminals.
}
To prevent contact welding, a fuse should be connected before the output contacts (see
}
Calculation of the max. cable length l
max
in the input circuit:
R
lmax
R
l
/ km
I
max
=
R
lmax
= max. overall cable resistance (see
)
R
l
/ km = cable resistance/km
}
Use copper wiring with a temperature stability of 60/75 °C.
}
To prevent EMC interferences (particularly common-mode interferences) the measures
described in EN 60204-1 must be executed. This includes the separate routing of cables
of the control circuits (input, start and feedback loop) from other cables for energy trans-
mission or the shielding of cables, for example.
}
Adequate protection must be provided on all output contacts with capacitive and inductive
loads.
}
Do not switch low currents using contacts that have been used previously with high cur-
rents.
}
Connect operational earth terminal to functional earth.
Important for detection of shorts across contacts:
As this function for detecting shorts across contacts is not failsafe, it is tested by Pilz during
the final control check. If there is a danger of exceeding the cable length, we recommend
the following test once the unit is installed:
1. Unit ready for operation (output contacts closed)
2. Short circuit the test terminals S22, S32 for detecting shorts across the inputs.
3. The unit‘s fuse must be triggered and the output contacts must open. Cable lengths in
the scale of the maximum length can delay the fuse triggering for up to 2 minutes.
4. Reset the fuse: Remove the short circuit and switch off the supply voltage for approx. 1
minute.