PNOZ X7.1
Operating Manual PNOZ X7.1
21003-EN-06
| 8
Function Description
The safety relay PNOZ X7.1 provides a safety-oriented interruption of a safety circuit. When
the supply voltage is applied via the E-STOP pushbutton, the “POWER” LED is lit. The unit
is ready for operation when the start circuit and feedback loop Y1-Y2 is closed.
}
Input circuit is closed (e.g. E-STOP pushbutton not operated):
– The LED "CH.1/CH.2" will light.
– The safety contact 13-14 is closed, the auxiliary contact 21-22 is open. The unit is
active.
}
Input circuit is opened (e.g. E-STOP pushbutton operated):
– The LEDs "CH.1" and "CH.2" goes out.
– Safety contact 13-14 is opened redundantly, auxiliary contact 21-22 is closed.
Operating modes
}
Single-channel operation: No redundancy in the input circuit, earth faults in the start and
input circuit are detected.
}
Automatic start: Unit is active once the input circuit has been closed.
}
Manual start: Unit is active once the input circuit and the start circuit are closed.
}
Increase in the number of available contacts by connecting contact expandsion modules
or external contactors/relays.
Timing diagram
[1]
[2]
Legend
}
Start: Start circuit
}
Power/Input: Supply voltage/input circuit
}
Output safe: Safety contact
}
Output aux: Auxiliary contact
}
[1]: Automatic start
}
[2]: Manual start
}
a: Input circuit closes before start circuit
}
b: Start circuit closes before input circuit
}
t
1
: Switch-on delay
}
t
2
: Delay-on de-energisation
}
t
3
: Recovery time