Times
787301
787302
Switch-on delay
With automatic start typ.
250 ms
340 ms
With automatic start max.
450 ms
400 ms
With automatic start after power
on typ.
250 ms
600 ms
With automatic start after power
on max.
450 ms
800 ms
With manual start typ.
125 ms
180 ms
With manual start max.
450 ms
400 ms
Delay-on de-energisation
With E-STOP typ.
15 ms
10 ms
With E-STOP max.
30 ms
20 ms
With power failure typ.
60 ms
–
With power failure max.
100 ms
–
With power failure typ. UB 240 V –
1100 ms
With power failure max. UB 240
V
–
1500 ms
With power failure typ. UB 24 V –
180 ms
With power failure max. UB 24 V –
230 ms
Recovery time at max. switching
frequency 1/s
After E-STOP
50 ms
50 ms
After power failure
200 ms
1500 ms
Supply interruption before de-ener-
gisation
20 ms
20 ms
Simultaneity, channel 1 and 2 max.
∞
∞
Environmental data
787301
787302
Climatic suitability
EN 60068-2-78
EN 60068-2-78
Ambient temperature
Temperature range
-35 - 55 °C
-10 - 55 °C
Storage temperature
Temperature range
-40 - 85 °C
-40 - 85 °C
Climatic suitability
Humidity
93 % r. h. at 40 °C
93 % r. h. at 40 °C
Condensation during operation
Not permitted
Not permitted
EMC
EN 60947-5-1, EN 61000-6-2, EN
61000-6-4, EN 61326-3-1
EN 60947-5-1, EN 61000-6-2, EN
61000-6-4, EN 61326-3-1
Vibration
In accordance with the standard
EN 60068-2-6
EN 60068-2-6
Frequency
10 - 55 Hz
10 - 55 Hz
Amplitude
0,35 mm
0,35 mm
Airgap creepage
In accordance with the standard
EN 60947-1
EN 60947-1
Overvoltage category
III / II
III / II
Pollution degree
2
2
Rated insulation voltage
250 V
250 V