Operation
Operating Manual PNOZ m ES EtherNet/IP
1003387-EN-05
20
7
Operation
When the supply voltage is switched on, the PNOZmulti safety system copies the configur-
ation from the chip card.
The LEDs “POWER”, “DIAG”, “FAULT”, “IFAULT” and “OFAULT” will light up on the base
unit.
The fieldbus module PNOZ m ES EtherNet/IP is configured and started automatically. The
LEDs "MS", "NS", "L/A1" and "L/A2" indicate the status of the PNOZ m ES EtherNet/IP on
the EtherNet/IP.
7.1
Messages
Legend
LED on
LED flashes
LED off
LED
Meaning
Power
green
Supply voltage is present
Supply voltage is not present
L/A1
green
Bus connection present at X1 (100 Mbit/s)
green
Data traffic present at X1 (100 Mbit/s)
orange
Bus connection present at X1 (10 Mbit/s)
orange
Data traffic present at X1 (10 Mbit/s)
Bus connection is not available at X1
L/A2
green
Bus connection present at X2 (100 Mbit/s)
green
Data traffic present at X2 (100 Mbit/s)
orange
Bus connection present at X2 (10 Mbit/s)
orange
Data traffic present at X2 (10 Mbit/s)
Bus connection not available at X2
MS
No supply voltage on PNOZ m ES EtherNet/IP
green
The fieldbus module PNOZ m ES EtherNet/IP is operating correctly
green
The fieldbus module PNOZ m ES EtherNet/IP is not configured
red
Recoverable fault
red
Major internal error (not recoverable)
green/red
Self test after switching on the supply voltage