![Pilz PNOZ m EF 4DI4DOR Operating Manual Download Page 15](http://html1.mh-extra.com/html/pilz/pnoz-m-ef-4di4dor/pnoz-m-ef-4di4dor_operating-manual_1556542015.webp)
Commissioning
Operating Manual PNOZ m EF 4DI4DOR
1002702-EN-08
| 15
6
Commissioning
6.1
General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Please note:
}
Information given in the
}
The position of the expansion module is specified in the Hardware configuration of the
PNOZmulti Configurator.
}
Use copper wiring with a temperature stability of 75 °C.
}
To prevent contact welding, a fuse should be connected before the output contacts (see
}
Sufficient fuse protection must be provided on all output contacts with capacitive and in-
ductive loads.
6.2
Connection
Input circuit
Single-channel
Dual-channel
Example:
E-Stop
without detection of shorts across
contacts
S1
I0
L+
S1
I1
I0
L+
L+
Example:
E-Stop
with detection of shorts across
contacts
I0
T0
S1
S1
T1
I1
T0
I0