Page 1: ...PNOZ m EF 16DI Operating Manual 1002703 EN 03 Configurable control systems PNOZmulti 2...

Page 2: ...KG Copies may be made for internal purposes Suggestions and comments for improving this documentation will be gratefully received Pilz PIT PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET...

Page 3: ...y 9 3 3 4 Disposal 9 3 3 5 For your safety 9 Section 4 Function description 10 4 1 Integrated protection mechanisms 10 4 2 Functions 10 4 3 System reaction time 10 4 4 Block diagram 10 Section 5 Insta...

Page 4: ...hat is particularly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates pre...

Page 5: ...Introduction Operating Manual PNOZ m EF 16DI 1002703 EN 03 5 INFORMATION This gives advice on applications and provides information on special fea tures...

Page 6: ...ulti Configurator 16 inputs for connecting for example E STOP pushbutton Two hand button Safety gate limit switch Start button Light beam devices Scanner Enabling switch PSEN Operating mode selector s...

Page 7: ...Overview Operating Manual PNOZ m EF 16DI 1002703 EN 03 7 2 3 Front view Legend Inputs I0 I15 LEDs POWER Run Diag Fault I Fault...

Page 8: ...trial environment The product may cause interference if installed in other environments If installed in other environments measures should be taken to comply with the applicable standards and directiv...

Page 9: ...invalid if The product was used contrary to the purpose for which it is intended Damage can be attributed to not having followed the guidelines in the manual Operating personnel are not suitably quali...

Page 10: ...ircuit to the base unit The base unit has 2 microcontrollers that monitor each other They evaluate the input circuits on the base unit and expansion modules and switch the outputs on the base unit and...

Page 11: ...ply with EMC requirements the mounting rail must have a low impedance con nection to the control cabinet housing The ambient temperature of the PNOZmulti units in the control cabinet must not exceed t...

Page 12: ...ules is defined in the PNOZmulti Configurator The ex pansion modules are connected to the left or right of the base unit depending on the type Please refer to the document PNOZmulti System Expansion f...

Page 13: ...nel Example E Stop without detection of shorts across contacts S1 I0 L S1 I1 I0 L L Example E Stop with detection of shorts across contacts I0 T0 S1 S1 T1 I1 T0 I0 6 3 Download modified project to the...

Page 14: ...POWE R Run Diag Fault IFault No supply voltage Expansion module PNOZ m EF 16DI is running without error Expansion module PNOZ m EF 16DI is in a STOP condition Internal error on the expansion module PN...

Page 15: ...urrent range 2 5 5 3 mA Pulse suppression 0 5 ms Maximum input delay 8 ms Potential isolation No Environmental data Ambient temperature In accordance with the standard EN 60068 2 14 Temperature range...

Page 16: ...erial Bottom PC Front PC Top PC Connection type Spring loaded terminal screw terminal Mounting type plug in Conductor cross section with screw terminals 1 core flexible 0 25 2 50 mm 24 12 AWG 2 core w...

Page 17: ...r Logic CPU PL e Cat 4 SIL CL 3 2 84E 10 20 Input SC inputs 1 channel PL d Cat 2 SIL CL 2 2 10E 09 20 SC inputs 2 channel PL e Cat 4 SIL CL 3 4 27E 11 20 SC inputs 1 ch pulsed light barrier PL e Cat 4...

Page 18: ...xpansion module 772 140 9 2 Accessories Connection terminals Product type Features Order No Set spring terminals 1 set of spring loaded terminals 751 004 Set screw terminals 1 set of screw terminals 7...

Page 19: ...p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document dependin...