PNOZ 16SP
Operating Manual PNOZ 16SP
19900-EN-05
10
}
Automatic start: Unit is active once the input circuit has been closed.
}
Manual start: Unit is active once the input circuit and the start circuit are closed.
}
Operating with pressure sensitive mat: When the pressure sensitive mat is actuated, a
short is formed between the inputs and internal fault detection is energised. Safety con-
tacts open and the "EXT.FAULT" LED is lit. If the pressure sensitive mat is cleared and
supply voltage is maintained, the unit is ready for operation again once the recovery
time has elapsed.
}
Increase in the number of available contacts by connecting contact expander modules
or external contactors/relays.
Timing diagram
[1]
[2]
Legend
}
Power: Supply voltage
}
Start: Start circuit
}
Input: Input circuit
}
Output safe: Safety contacts
}
Semi FAULT: Semiconductor output short across contact
}
Semi OUT: Semiconductor output switch state
}
FAULT: Short across contacts in the input circuit due to actuation of pressure sensitive
mat
}
[1]: Automatic start
}
[2]: Manual start
}
a: Input circuit closes before start circuit
}
b: Start circuit closes before input circuit
}
t
1
: Switch-on delay
}
t
2
: Delay-on de-energisation
}
t
3
: Recovery time after short across contacts