PZA
Operating Manual PZA
18219-EN-07
25
Relay outputs
774028
774029
Utilisation category of auxiliary con-
tacts
AC1 at
240 V
240 V
Min. current
0,01 A
0,01 A
Max. current
6 A
6 A
Max. power
1500 VA
1500 VA
DC1 at
24 V
24 V
Min. current
0,01 A
0,01 A
Max. current
6 A
6 A
Max. power
150 W
150 W
Utilisation category
In accordance with the standard
EN 60947-5-1
EN 60947-5-1
Utilisation category of safety con-
tacts
AC15 at
230 V
230 V
Max. current
4 A
4 A
DC13 (6 cycles/min) at
24 V
24 V
Max. current
3 A
3 A
Utilisation category of auxiliary con-
tacts
AC15 at
230 V
230 V
Max. current
4 A
4 A
DC13 (6 cycles/min) at
24 V
24 V
Max. current
3 A
3 A
Utilisation category in accordance
with UL
Voltage
240 V AC G. P.
240 V AC G. P.
With current
6 A
6 A
Voltage
24 V DC Resistive
24 V DC Resistive
With current
5 A
5 A
Pilot Duty
B300, R300
B300, R300
External contact fuse protection,
safety contacts
In accordance with the standard
EN 60947-5-1
EN 60947-5-1
Max. melting integral
240 A²s
240 A²s
Blow-out fuse, quick
6 A
6 A
Blow-out fuse, slow
4 A
4 A
Blow-out fuse, gG
6 A
6 A
Circuit breaker 24V AC/DC,
characteristic B/C
4 A
4 A