Commissioning
Operating Manual PNOZ m EF 4AI
1004650-EN-02
| 26
6
Commissioning
6.1
Wiring
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Please note:
}
Information given in the
Technical details [
34]
must be followed.
}
The position of the expansion module is specified in the Hardware configuration of the
PNOZmulti Configurator.
}
Use copper wiring with a temperature stability of 75 °C.
}
The power supply that feeds the expansion module and the sensors must meet the regu-
lations for extra low voltages with protective electrical separation (SELV, PELV).
}
Supply connections
The 6 supply connections 24 V and 0 V to the terminal blocks X3 and X4 are interconnec-
ted internally.
– The supply of the analogue input module PNOZ m EF 4AI has to be made via the
supply connections 24 V and 0 V at the terminal block X4.
– The other supply connections can be used for the supply of the sensors.
}
Protect the supply voltage as follows:
– Circuit breaker, characteristic C – 2 … 6 A
or
– Blow-out fuse, slow, 2 … 6 A
}
Use shielded, twisted pair cable for the connections on the input current circuits.
}
Separate the supply voltage cable from the analogue input current lines.
}
For transducers located outside the control cabinet:
Where the cable enters the con-
trol cabinet, the cable shield
must
be connected to the earth potential over a wide sur-
face area and with low impedance (connect in star).
6.2
Connection
Supply voltage
Supply voltage
DC