Wiring
General guidelines
}
Do not lay the connecting cable near or in contact with cables that carry high or highly
volatile currents.
}
Use separate cables to connect the wires to the OSSDs on different safety light curtains
or safety switches.
}
Do
not
connect contacts OSSD1 and OSSD2 in series or in parallel.
}
For supply voltage, use only PELV/SELV power supplies that have a voltage buffer in ac-
cordance with EN 60204-1.
}
The power supply must be able to bridge a short (20 ms) supply voltage failure in accord-
ance with EN 61496-1.
}
SELV power supply
– Do
not
connect the safety light curtain housing to the earth conductor or the protect-
ive conductor. The transmitters and receivers must be electrically isolated from the
machine/system. The use of the flexible bracket (swivel mount) provides this electrical
isolation.
}
Connection to PDP67
– Use the order reference of the cable listed (see
)
}
Connection to other evaluation devices
– Use the order reference of the cable listed (see
Accessories, connection to other
– The clamps for connection to the evaluation device must be kept in a locked control
cabinet. This prevents unauthorised modifications.
}
Ensure compliance with permissible cable bending radii (see
Connector pin assignment
Transmitter and receiver electrical connections are made with M12 connectors. These con-
nectors are located on the bottom of the transmitters and receivers.
5-pin connector on the transmit-
ter
PIN
Assignment
Cable colour
1
2
3
4
5
1
uncoded: +24 VDC
brown
A-coded: +24 V DC
B-coded: 0 V DC
2
Reserved
white
3
0 VDC
blue
4
Reserved
black
5
uncoded: +24 VDC
grey
A-coded: 0 V DC
B-coded: +24 V DC