Examples for connection to Pilz evaluation devices:
I0
I1
PNOZmulti
PSENmag
3+
1
2
4
T1
T0
3
1
2
4
11
12
13
14
PSEN i1
Brown
White
Blue
Black
Legend
I0 Input OSSD
I1 Input OSSD
T1, T2 Test pulse outputs
Installation
CAUTION!
Potential loss of safety function due to changed device properties
The unit's properties may be affected if installed in an environment contain-
ing electrically or magnetically conductive material.
– Please check the operating distances and the assured release dis-
tance.
CAUTION!
Possible loss of the safety function by changing the release distance S
ar
with non-flush installation
Installing the safety switch non-flush within electrically or magnetically con-
ductive material, the value for the assured release distance
S
ar
can change.
– Check the assured release distance
S
ar.
}
Safety switches and actuators must be positioned so that they are secured against a
change of position.
}
Avoid the risk of damages from foreseeable external influences by attaching the safety
switch and actuator. If necessary, safety switch and actuator have to be protected.
INFORMATION
The actuator should be protected from unauthorised removal and from con-
tamination.
}
Prevent self-loosening of the fastening elements of safety switch and actuator.