Pilz 506 240 Operating Manual Download Page 17

PSEN ma1.3a/b-21 VA

Operating Manual PSEN ma1.3a/b-21 VA
1004515-EN-02

17

Environmental data

506240

506242

Vibration

In accordance with the standard

EN 60947-5-2

EN 60947-5-2

Frequency

10 - 55 Hz

10 - 55 Hz

Amplitude

1 mm

1 mm

Shock stress

Acceleration

30g

30g

Duration

11 ms

11 ms

Airgap creepage

Pollution degree

3

3

Rated insulation voltage

30 V

30 V

Rated impulse withstand voltage

0,8 kV

0,8 kV

Protection type

Housing

IP67, IP69

IP67, IP69

Mechanical data

506240

506242

Actuator 1

PSEN ma1.3-08 VA

PSEN ma1.3-08 VA

Typ. Hysteresis

3 mm

3 mm

Operating distances

Assured operating distance Sao

8 mm

8 mm

Min. operating distance Somin

0,5 mm

0,5 mm

Typical operating distance So

10 mm

10 mm

Assured release distance Sar

18 mm

18 mm

Typical release distance Sr

13 mm

13 mm

Repetition accuracy switching
distances

5 %

5 %

Min. distance between safety
switches

25 mm

25 mm

Sensor flush installation in accord-
ance with EN 60947-5-2

Yes, follow installation
guidelines

Yes, follow installation
guidelines

Connection type

5 m cable

10 m cable

Cable

Li9Y11Y 6 x 0.14 mm2

Li9Y11Y 6 x 0.14 mm2

Material

Top

Stainless steel 1.4401

Stainless steel 1.4401

Max. torque setting

Safety switch

20 Nm

20 Nm

Actuator 1

20 Nm

20 Nm

Dimensions

Height

12 mm

12 mm

Width

12 mm

12 mm

Depth

76 mm

76 mm

Actuator dimensions

Height

12 mm

12 mm

Width

12 mm

12 mm

Depth

25 mm

25 mm

Weight of safety switch

120 g

220 g

Weight of actuator

10 g

10 g

Summary of Contents for 506 240

Page 1: ...PSEN ma1 3a b 21 VA Operating Manual 1004515 EN 02 PSEN sensor technology...

Page 2: ...nta tion will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Internet...

Page 3: ...ed personnel 6 Warranty and liability 6 Disposal 6 For your safety 6 Unit features 7 Function description 7 Block diagram 7 Operating distances 8 Lateral and vertical offset 8 Wiring 9 Pin assignment...

Page 4: ...that is particularly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates pr...

Page 5: ...e technical details see Technical details 16 NOTICE EMC compliant electrical installation The product is designed for use in an industrial environment The product may cause interference if installed i...

Page 6: ...ty and liability will be rendered invalid if The product was used contrary to the purpose for which it is intended Damage can be attributed to not having followed the guidelines in the manual Operatin...

Page 7: ...c Switching voltage 24 VDC LED to display switch status Switch and actuator from stainless steel Function description If the actuator is within the response range safety gate closed the safety contact...

Page 8: ...Off Legend Sao Assured operating distance Somin Min operating distance Sar Assured release distance The offset independent values for the switching distances are included in the Technical details 16...

Page 9: ...s cable Ensure the wiring and EMC requirements of EN 60204 1 are met Depending on which evaluation device is used the overall cable resistance must be checked before commissioning it may also be neces...

Page 10: ...5P PNOZ X2 7P PNOZ X2 8P PNOZ X2 9P PNOZ X2C PNOZ X3 PNOZ X3 1 PNOZ X3P PNOZ X3 10P PNOZ X4 PNOZ X5 PNOZ X5J PNOZ Ex PNOZmulti for safety gate monitoring Configure the switch in the PNOZmulti Configur...

Page 11: ...have been opened and closed partial operation lock INFORMATION Risk time in accordance with DIN EN 60947 5 3 The risk time is made up of the reaction time of the sensor see Technical details 16 and t...

Page 12: ...sed lights No Open Off 1 2 3 4 5 6 24 V GND PSENmag 1 2 3 4 5 6 24 V PLC PSENmag Connecting the auxiliary contact to an eval uation device Connecting the auxiliary contact to a PLC Installation The un...

Page 13: ...el Avoid the risk of damages from foreseeable external influences by attaching the safety switch and actuator If necessary safety switch and actuator have to be protected INFORMATION Protect the actua...

Page 14: ...ght Installation of safety switch Sensing face Slide the switch through the hole in the mounting surface with the sensing face to wards the actuator Attach the switch using 2 M12x1 hexagonal nuts Also...

Page 15: ...ate if other arrangements are used Note the maximum permitted lateral and vertical offset see Operating distances and Lateral and vertical offset 8 Periodic test Carry out a monthly function test on t...

Page 16: ...p Ud 3 5 V 3 5 V Switching voltage 24 V 24 V Internal resistance safety contacts 10 Ohm 10 Ohm Max switching current safety con tacts 0 14 A 0 14 A Max breaking capacity safety con tacts 4 W 4 W Max s...

Page 17: ...n operating distance Somin 0 5 mm 0 5 mm Typical operating distance So 10 mm 10 mm Assured release distance Sar 18 mm 18 mm Typical release distance Sr 13 mm 13 mm Repetition accuracy switching distan...

Page 18: ...3 08 VA 1U Magnetic safety switch actuator with assured operating distance 8 mm Cable 5m 506 240 PSEN ma1 3b 21 PSEN ma1 3 08 VA 1U Magnetic safety switch actuator with assured operating distance 8 mm...

Page 19: ...NET p THE SPIRIT OF SAFETY are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document depen...

Reviews: