background image

    

 

APZ 2030 

Operation Manual

 

2.1.2 You can set spans for the device with control buttons found on the front 

panel. See Table 1 for basic and optional spans. 

  Table 1 - Spans 

Basic spans, Pa 

-500…+500 

-100…+2000 

0…7000 

Optional spans, Pa 

-100…+100 

-200…+200 

0…100 

0…200 

0…500 

-100…+100 

0…100 

0…200 

0…500 

0…1000 

0…2000 

0…1000 

0…1500 

0…2000 

0…3000 

0…5000 

Burst pressure, kPa 

±10 

±30 

±80 

Burst pressure, kPa 

±20 

±40 

±100 

2.1.3 See Table 2 for output signal parameters. 

Table 2 - Output parameters 

Parameter 

Value (properties) 

    Analog outputs:

 

Number of measuring channels 

Voltage

output 

(3-wire) / load resistance 

0...10 V / ≥10 kOhm

 

Current

output 

(3-wire) / load resistance 

4...20 mA / ≤ 500 Ohm

 

    Switch outputs:

 

Number of switch outputs 

2 (independent) 

Type of mechanical switch contact 

nonbridging 

(NC and NO) 

Max switching voltage 

250 V (AC) / 30 V (DC) 

Max switching current (contact type) 

5 A (NO)/3 A (NC) 

Switched signals (active load): 

 - DC, voltage of 30 V 

 - AC, voltage of 250 V 

5 A (NO)/3 A (NC) 

5 A (NO)/3 A (NC) 

Tripping threshold (configurable), % of span 

0…100 

Switch operating modes (configurable) 

hysteresis/window 

Switching accuracy 

±0.7% 

2.1.4. The device has a display, see Table 3 for its specifications. 

Table 3 - Display specifications 

Name 

Value 

Range of displayed values 

-19999…+19999 

Primary / secondary line height 

15/7 mm 

Displayed accuracy 

0.1% of span ± low-

order digit as % of span 

Readings display time, max 

0.2 s 

2.1.5 DC power supply voltage ranges from 18 to 36 V (rated - 24 V), AC - 24 

V ± 10%. 

2.1.6  Consumed current/power, max - 100 mA/3.6 W. 

2.1.7 Dimensions, max - 106 × 91 × 44 mm (Supplement A). 

2.1.8 Weight, max - 0.25 kg. 

2.1.9 Housing ingress protection (GOST 14254) - IP66. 

 

2.2. Operating conditions: 

2.2.1 The device was designed to operate in the following conditions: 

- enclosed explosion-proof spaces free from aggressive vapors and gases;

 

- ambient temperature from -

10 to +50 °С;

 

- medium temperature from -

5 to + 65 °C;

 

- atmospheric pressure from 84 to 106.7 kPa. 

2.2.2 Medium: air, non-flammable and non-aggressive gases. 

2.2.3 Resistance to atmospheric pressure puts the device in group R1 under 

GOST R 52931 (max height above sea level - 1000 m). 

2.2.4 Resistance to mechanical attack puts the device in group N2 under 

GOST R 52931. 

2.3 Operating limitations:

 

-  medium should be free from crystallizable impurities, contaminations and 

dust;

 

- medium should be free from flammable and aggressive gases and liquids.  

3 Safety precautions 

3.1 The electric shock hazard class of the device is III (no dangerous voltage); 

see GOST 12.2.007.0 for full classification.  

3.2 Take measures to prevent moisture from getting into the housing. 

3.3 Only qualified specialists that have read and understood this manual are 

allowed to mount, connect, adjust, do maintenance on the device. 

4  Mounting and use 

4.1 Mount the device onto a vertical surface through two Ø5 mm holes (see 

Supplement A). Make sure its pressure port and cable glands point downwards 

(to allow condensate draining).  

4.2  See Figure 1 for circuits connection diagram (connected inside the 

housing via cable glands). 

Figure 1 - 

Connection diagram; P1, P2 

- inlet medium pressure, P1 (+) for 

higher pressure, P2 (-) for lower pressure. 

This manual covers mounting and operation of APZ 2030 differential pressure 

transmitter (hereinafter 

referred  to  as  "transmitter"  or  "device");  it  contains 

technical data, description of design and other information necessary for 

proper application and maintenance of the device. 

See datasheets at http://piezus.ru for complete specifications.

 

Production regulated by TOR 4212-000-7722857693–2015. 

Terms and abbreviations used in the manual: 

Span  – 

measurement  range;  NC 

normally  closed  (NC  contact);

 

NO - 

normally open (NO contact); SW1, SW2 

- switch contacts. 

1  Purpose of the device 

1.1 APZ 2030 differential pressure transmitter finds application in monitoring, 

protection, alarm and control systems in heat and power installations, air 

conditioning systems, various industrial environments and public utilities.  
1.2  The device:  

-  proportionally and linearly converts measured differential pressure and 

outputs normalized voltage (0 ... 10 V) and current (4 ... 20 mA) signals;

 

- compares current pressure value to the preset thresholds and outputs two 

switching signals when the monitored parameter crosses those thresholds (as 

prescribed by the selected operation algorithm, hysteresis or window); 

 

- shows current pressure value (in selected units) and discrete outputs status 

on the integrated digital display. Display and buttons allow quick 

reconfiguration of the device and eliminate the need to unmount it for that 

purpose. 
1.3 Applications - heating, ventilation and air conditioning systems (HVAC/R): 

monitoring of flows in ventilation ducts;

 

- control of exhaust and discharge fans in air 

ducts; 

 

- differential pressure control in filters 

air pressure control in clean rooms;

 

air supply and fire flaps control;

 

overheating protection for ventilation heaters;

 

- HVAC systems emergency control. 

2 Technical specifications 

2.1  General technical data 

2.1.1 See transmitter's passport and label (sticker) for basic span and accuracy 

info.

 

www.piezus.ru 

PRESSURE TRANSMITTER

 

Summary of Contents for APZ 2030

Page 1: ...II no dangerous voltage see GOST 12 2 007 0 for full classification 3 2 Take measures to prevent moisture from getting into the housing 3 3 Only qualified specialists that have read and understood this manual are allowed to mount connect adjust do maintenance on the device 4 Mounting and use 4 1 Mount the device onto a vertical surface through two Ø5 mm holes see Supplement A Make sure its pressur...

Page 2: ...ning purposes Routine checkups of the device in use follow data specified in its passport See the device s passport for its calibration interval and manufacturer s warranty Manufacturer refuses all claims reclamations complaints related to devices with damaged manufacturer seals and showing signs of damage resulting from inappropriate operation transportation or storage All and any repairs are don...

Page 3: ...r below it its code or value Figure 1 Figure 1 Displayed elements Operation parameters setup mode R1HI signal threshold for SW1 switch contacts activation Press ENTER MENU button to browse the parameters Press ESC to edit a parameter its code or value starts flashing Press UP and DOWN buttons to change code value press and hold any of them to have the figure change rapidly in the appropriate direc...

Page 4: ...lected span 5 press and hold ESC to exit the menu EXAMPLE 2 Setting the switch response delay 1 Press and hold ENTER MENU to enter the menu 2 switch to RESP by pressing DOWN 3 enter RESP editing mode by pressing ENTER MENU 4 press UP and DOWN to set the delay in seconds affects both switches 5 press ENTER MENU to save the setting 6 press and hold ESC to exit the menu EXAMPLE 3 Selecting switch ope...

Reviews: