7 Start-Up
44
Version: 2.0.0
MS205Equ
C-863 Mercury Controller
7.2.3 Baud Rate
Baud rate*
S5
S6
9600
ON
ON
19200
ON
OFF
38400
OFF
ON
115200
OFF
OFF
*Factory settings are shown in bold.
INFORMATION
The same baud rate must be set for every controller in a daisy chain network.
7.2.4 Logic Level of the Limit Switches
Limit switches (hardware
setting)*
S7
Active low
ON
Active high
OFF
*Factory settings are shown in bold.
INFORMATION
The C-863 can be adapted via DIP switch 7 and the
Limit Mode
parameter (ID
0x18) to the logic level of the limit switches of the stage connected (active high or
active low). In order for the stage to be able to move, the DIP switch
and
parameter
settings must correspond to the logic level of the limit switches.
DIP switch 7 is preset for using active high signals (e. g. for DC motor stages from
PI). If you select your PI stage from a stage database in the PC software from PI, the
Limit Mode
parameter is already set correctly.