Photonic Universe AGM-DC-2V500AH Instruction Manual Download Page 2

 

2

 

Use  a  separate 

Installation  manual  for  the  48V  battery  bank  on  a  rack

  for  details  about  assembly, 

installation and connection of the battery bank and the racking unit. This separate manual is included in your 

battery bank delivery. 

Make  sure  you  always  tighten  the  terminals  well.  Loose connections  reduce  performance,  generate  heat 

and increase the risk of fire.   

After your battery bank has been assembled, put covers on top of batteries (if they are included with your 

batteries) and make sure that there are no other objects above the battery bank which might fall on it.   

 

 

 

 

 

 

 

III. CHARGE & DISCHARGE 

(data and values are provided per 1 battery)

 

 
A) 

CHARGE 

 

For Cycle Use 

(when the battery is used as a regular power source and it’s discharged / charged frequently)

 

Charging voltage (at 25 ⁰C) 

Initial charging current 

Temperature coefficient 

2.30V – 2.35V 

100A max 

-5mV/⁰C 

If the battery is in cycle use, it is important to fully charge it regularly to minimise sulphation that may cause a 

reduction in battery capacity. For best results use an intelligent multi-stage battery charger / charge controller 

and make sure the battery is charged all the way to the final stage.   

 

 

For Standby Use 

(when the battery is mainly used as an emergency power source)

 

Charging voltage (at 25 ⁰C) 

Initial charging current 

Temperature coefficient 

2.26V – 2.28V 

100A max 

-3mV/⁰C 

Note: at the end of charging, the battery will generate flammable gas. Avoid using the battery near sources 

of heat, sparks or in closed containers. 

 

B) Discharging Current & Cut-off Voltage

 

In order to extend the lifetime of your battery, please do not allow it to get discharged completely. The final 

battery voltage at which you should disconnect any load and stop discharging the battery depends on the 

discharging current:

 

Discharging Current (A) 

< 10A 

10A - 80A   

80A - 120A 

120A - 300A 

> 300A 

Load cut off voltage (V) 

1.85V 

1.8V 

1.75V 

1.7V 

1.6V 

IV. HANDLING INSTRUCTIONS 

 

A) Storage and refresh charge   

1. Store the battery in a cool, dry place 

2. During storage, the charge held by the battery decreases due to constant self-discharging. When the 

monthly average temperature is more than 25°C but less than 40°C, please carry out supplementary 

charging every 3 months. When the monthly average temperature falls below 25°C, please carry out 

supplementary charging every 6 months. 