background image

4

www.thermastor.com • [email protected]

Toll-Free 1-800-533-7533

To adjust the defrost timer:
.   Unplug the unit.
2.   Remove the top panel and the front cover (6 screws).
3.   The timer is fastened to the base at the front of the 

unit. Every third peg around the dial is pushed out 
from the dial center except one section with 4 pegs 
out in a row. The grain control (8 holes at the intake 
of the unit below the filter) should be open. Refer to 
Figures 3 and 4.

4.   To improve performance below 50°F, the compressor 

“off” time must be increased to allow the frost to 
completely melt. To do this, push the pegs out from 
the dial center so that the pegs alternate with 2 
toward the center, then 2 out from the center, all the 
way around the dial except for the section now with 6 
pegs out in a row. Refer to Figure 4.

5.   Replace the cover and top panel.

2.10  Low Pressure Control

If the low side refrigerant pressure drops to 5 PSIG, the 
low pressure control opens and shuts off the compressor 
and blower. It is an automatically reset control. Its primary 
function is to prevent damage to the compressor if a leak 
develops in the refrigeration system. It may also open if 
the unit is A) used in a cool area (below 50°F) and the 
defrost timer is not adjusted or B) stored where it is below 
40°F and then started. Under these conditions, the unit 
will restart within several minutes; it may cycle several 
times until the unit warms up.

3 Maintenance

3.1 Air Filter

The Phoenix Arctic Max is equipped with 2 pleated fabric 
air filters that must be checked regularly. The cooling air 
flow filter is a MERV- high efficiency filter. The condener 
exhaust filter is a MERV-7. Operating the unit with a dirty 
filter will reduce the dehumidifier’s capacity and efficiency 
and may cause the compressor to cycle off and on 
unnecessarily on the defrost control.

The filter can generally be vacuumed clean several times 
before needing replacement. Replacement filters can be 
ordered from the factory or purchased locally if available.

WARNING: DO NOT operate the unit without the filter or 
with a less effective filter as the heat exchange coils inside 
the unit could become clogged and require disassembly to 
clean.

3.2 Storage

There are two issues to consider when the Phoenix Arctic 
Max is stored between uses and both pertain to the 
water trapped in the unit: damage caused by freezing or 
biological growth.
The effect of the trapped water can be greatly reduced 
if precautions are taken to remove as much as possible 
before storage.
.   Use the pump purge switch to reduce the water level 

in the reservoir.

2.   Stretch the hose flat to drain it completely.
If the unit will not be exposed to freezing temperatures, an 
alternative to reduce biological growth is to flush the unit 
with a bio-fungicide that is approved for use with copper, 
aluminum and polyethylene. To flush:
.   Run the hose to a drain.
2.   Remove the air filter. Remove top and front cover.

Slowly pour a quart of the chemical through the 
evaporator coil fins and drain into the drain pan.

3.  Flush coil with water.
4.   Hold in the pump purge switch to reduce the water 

level in the reservoir.

4 Service

WARNING: Servicing the Phoenix Arctic Max with its high 
pressure refrigerant system and high voltage circuitry 
presents a health hazard which could result in death, 
serious bodily injury, and/or property damage. Only 
qualified service people should service this unit. 
Do not operate unit without the front panel in place.

4.1 Technical Description

The Phoenix Arctic Max uses a refrigeration system similar 
to an air conditioner’s to remove heat and moisture from 
incoming air and to add heat to the air that is discharged.
Hot, high pressure refrigerant gas is routed from the 
compressor to the condenser coil. The refrigerant is cooled 
and condensed by giving up its heat to the air that is about 
to be discharged from the unit. The refrigerant liquid then 
passes through a filter/drier and capillary tubing which 

Figure 4: Defrost timer 
for operating in tempera-
tures 

below

 50°F.

Figure 3: Defrost timer 
for operating in tem-
peratures 

above

 50°F.

Summary of Contents for Arctic Max TS-388

Page 1: ...humidifiers When used in conjunction with the Phoenix Solution LGR performance amplifier the Phoenix Arctic Max provides a reliable cooling air stream to maximize overall performance The Phoenix Arcti...

Page 2: ...s carefully before using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your Phoenix Arctic Max dehumidifier It is designed to be used INDOORS ONLY If use...

Page 3: ...ng into vehicles 2 2 Electrical Requirements The Phoenix Arctic Max plugs into a common grounded outlet on a 15 Amp circuit It draws 11 7 Amps at 95 F 60 RH If used in a wet area a ground fault interr...

Page 4: ...be ordered from the factory or purchased locally if available WARNING DO NOT operate the unit without the filter or with a less effective filter as the heat exchange coils inside the unit could become...

Page 5: ...3 Loose connection in compressor circuit 4 Defective compressor overload 5 Defective compressor 6 Defective relay Figure 5 Refrigeration system No dehumidification blower runs but compressor does not...

Page 6: ...h or if the pump purge switch is held in To replace the condensate pump 1 Remove the metal strap holding the pump by loosening the 2 screws holding it in place 2 Disconnect the leads 3 Installation is...

Page 7: ...r LLC PO BOX 8680 MADISON WI 53708 CAP YEL RED WHT WHT WHT BLU COMPRESSOR COMP BLK BLOWER CONTROL BLK BLK 5 3 2 MOTOR DEFROST 1 TIMER MOTOR SWITCH TIMER WHT VIO 1 DEFROST TIMER CONTROL THERMOSTAT BLK...

Page 8: ...254 15 Condensate Pump 1 4023649 16 10 Wire Duct Collar Cooling 1 4024078 17 Top 1 4026842 18 Handle Assembly 1 4026094 19 Pump Purge Switch 1 4021796 20 Hour Meter 1 4021597 21 Power Switch 1 4021822...

Page 9: ...s warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident...

Reviews: