Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Noise emission according to EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
CE basic standard
Minimum normative
requirements
Higher requirements in
practice (covered)
Conducted noise emission EN 55016
EN 61000-6-4 (Class A)
EN 61000-6-3 (Class B)
Noise emission EN 55016
EN 61000-6-4 (Class A)
EN 61000-6-3 (Class B)
Noise emission for marine approval
Minimum normative
requirements of DNV GL
Higher requirements in
practice of DNV GL (cov
-
ered)
DNV GL conducted noise emission
Class A
Area power distribution
Class B
Bridge and deck area
DNV GL noise radiation
Class A
Area power distribution
Class B
Bridge and deck area
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station
equipment zone), IEC/EN 61850-3 (energy supply)
CE basic standard
Minimum normative
requirements of
EN 61000-6-2 (CE)
(immunity for industrial
environments)
Higher requirements in
practice (covered)
Electrostatic discharge EN 61000-4-2
Housing contact discharge
4 kV (Test Level 2)
6 kV (Test Level 4)
Housing air discharge
8 kV (Test Level 3)
8 kV (Test Level 3)
Comments
Criterion B
Criterion A
Electromagnetic HF field EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
80 MHz ... 1 GHz
Test field strength
10 V/m (Test Level 3)
20 V/m (Test Level 3)
Frequency range
1 GHz ... 6 GHz
1 GHz ... 6 GHz
Test field strength
3 V/m (Test Level 2)
10 V/m (Test Level 3)
Comments
Criterion A
Criterion A
Fast transients (burst) EN 61000-4-4
Input
2 kV (Test Level 3 -
asymmetrical)
2 kV (Test Level 4 -
asymmetrical)
Output
2 kV (Test Level 3 -
asymmetrical)
2 kV (Test Level 4 -
asymmetrical)
Signal
1 kV (Test Level 3 -
asymmetrical)
2 kV (Test Level 4 -
asymmetrical)
Comments
Criterion B