![Phoenix Contact IB IL 24/230 DOR 1/W Datasheet Download Page 13](http://html1.mh-extra.com/html/phoenix-contact/ib-il-24-230-dor-1-w/ib-il-24-230-dor-1-w_datasheet_1551624013.webp)
onlinecomponents.com
IB IL 24/230 DOR 1/W
5663BC01
13
Technical Data
General Data
Housing dimensions (width x height x depth)
12.2 mm x 120 mm x 71.5 mm
(0.480 in. x 4.724 in. x 2.815 in.)
Weight
46 g (without connector)
Operating mode
Process data operation with 2 bits
Connection method for actuators
To an electrically isolated relay changeover
contact
Permissible temperature (operation)
-25°C to +55 °C (-13°F to +131°C)
Permissible temperature (storage/transport)
-25°C to +85°C (-13°F to +185°F)
Permissible humidity (operation)
75%, on average, 85%, occasionally
In the range from -25°C to +55°C (-13°F to +131°F) appropriate measures against
increased humidity (> 85%) must be taken.
Permissible humidity (storage/transport)
75%, on average, 85%, occasionally
For a short period, slight condensation may appear on the housing if, for example, the
terminal is brought into a closed room from a vehicle.
Permissible air pressure (operation)
80 kPa to 106 kPa
(up to 2000 m [6561.680 ft.] above sea level)
Permissible air pressure (storage/transport)
70 kPa to 106 kPa
(up to 3000 m [9842.520 ft.] above sea level)
Degree of protection
IP 20 according to IEC 60529
Interface
INTERBUS local bus
Through data routing
Power Consumption
Communications power
7.5 V
Current consumption from the local bus
60 mA, maximum
Power consumption from the local bus
0.45 W, maximum
Supply of the Module Electronics and I/O Through Bus Terminal/Power Terminal
Connection method
Through potential routing