Application manual for PSRclassic and PSRmultifunction, and the modular safety relay system
PHOENIX CONTACT
102597_en_03
5.2.3
PSR-ESAM4/8x1/1x2 up to PL e/SIL 3
Two-channel light grid monitoring with automatic reset (ESPE type 4)
Application example
–
Two-channel light grid monitoring
–
Cross-circuit detection via the light grid
–
Manual reset (S33, S35)
–
Feedback of contactor contacts K3 and K4 at S33 and S35
–
Stop category 0
–
Monitoring of external contactors
–
Safety level of the example up to PL e (EN ISO 13849-1) and SIL 3 (EN 62061)
Figure 5-11
Two-channel light grid monitoring with automatic reset
PSR-ESAM4/8x1/1x2
Order No.
2963912 with screw connection
2963996 with spring-cage connection
Technical data
–
24 V AC/DC
–
8 enabling current paths, 1 signaling current path
–
Monitored manual start or autostart
–
Reinforced insulation/basic insulation
–
Cat. 4/PLe in accordance with EN ISO 13849-1, SILCL 3 in
accordance with EN 62061