background image

RAD-....-IFS

82 / 198

PHOENIX CONTACT

105542_en_05

6.6.10

RSSI signal and error code registers

The RSSI values indicate the received signal strength on the wireless module. You can read 

the RSSI values via the serial interface of the master wireless module (RAD ID = 01) using 

Modbus/RTU commands. The RSSI values of all wireless modules in the network are within 

address range 35001 ... 35250.

Bit 08 = error on IFS bus

If an error is present on the IFS bus, the register value is 1 (e.g., local bus error, because the 

input or output module is disconnected from the DIN rail connector). If no error is present on 

the IFS bus, the register value is 0.

Bits 9 ... 15 are reserved.

Values  <255  indicate  the RSSI value in -dBm.

Value 255 means that the RSSI value is invalid or the device cannot be reached.

Example for reading the RSSI register of the station with RAD ID = 2:

Function code 04, start address 5001 (hex1389)

Table 6-17

RSSI signal and error code registers

Address range

35001 ... 35250

Modbus function code

fc 04

Address

Wireless module

High byte

Low byte, RSSI value

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

35001

RSSI - RAD ID = 1

(master)

Reserved

IFS

X

X

X

X

X

X

X

X

35002

RSSI  -  RAD  ID  =  2

Reserved

X

X

X

X

X

X

X

X

...

...

Reserved

X

X

X

X

X

X

X

X

35250

RSSI  -  RAD  ID  =  250

Reserved

X

X

X

X

X

X

X

X

Summary of Contents for 2702863

Page 1: ...User manual UM EN RAD IFS Radioline Wireless transmission system for serial interfaces and I O signals...

Page 2: ...nd I O signals Designation Order No Wireless modules RAD 2400 IFS 2901541 RAD 868 IFS 2904909 RAD 2400 IFS JP 2702863 I O extension modules RAD AI4 IFS 2901537 RAD PT100 4 IFS 2904035 RAD AO4 IFS 2901...

Page 3: ...structure 19 3 2 Basic circuit diagram 20 3 3 Mounting and removal 20 3 4 Connecting the cables 22 3 5 Connecting the power supply 23 3 6 Serial interfaces 24 3 7 Connecting the antenna 27 4 Configur...

Page 4: ...uts 98 7 4 RAD DI4 IFS digital extension module with four inputs 102 7 5 RAD DI8 IFS digital extension module with eight inputs 106 7 6 RAD DOR4 IFS digital extension module with four outputs 111 7 7...

Page 5: ...s 151 9 1 Loopback test during serial data transmission 157 10 Technical data for the wireless modules 159 A Technical appendix 171 A 1 Typical combinations of antennas and adapter cables 171 A 2 Cont...

Page 6: ...RAD IFS 6 198 PHOENIX CONTACT 105542_en_05...

Page 7: ...symbol indicates hazards that could lead to personal injury There are three signal words indicating the severity of a potential injury DANGER Indicates a hazard with a high risk level If this hazardo...

Page 8: ...ng license You can find the approved accessories for this wireless system listed with the product at phoenixcontact net products 1 3 2 RAD 2400 IFS wireless module Please note that in combination with...

Page 9: ...ndanger your safety or damage the device Do not repair the device yourself If the device is defective please contact Phoenix Contact The RAD 2400 IFS JP wireless module is only approved for use in Jap...

Page 10: ...al loads that exceed the specified limits To protect the device against mechanical or electrical damage install it in suitable housing with an appropriate degree of protection according to IEC 60529 T...

Page 11: ...or the transmission power The HF cable to the antenna must be suitable for the ambient conditions Install the ca ble so that it is protected against mechanical damage corrosion chemical stress and neg...

Page 12: ...D These devices are open type devices that are to be installed in an enclosure suit able for the environment that is only accessible with the use of a tool E WARNING Exposure to some chemicals may de...

Page 13: ...ollowing two conditions 1 this device may not cause interfer ence and 2 this device must accept any interference including interference that may cause undesired operation of the device This device has...

Page 14: ...this equipment or device must accept any interference including interference that may cause its undesired operation This equipment has been designed to operate with antennas listed below and for an an...

Page 15: ...data can therefore be distributed across vari ous media using the thumbwheel The PSI CONF configuration and diagnostic software for special functions and diagnostic options of the wireless module is a...

Page 16: ...re free of charge at phoenixcontact net products Table 2 1 Firmware versions Function As of firmware version RAD 2400 IFS RAD 868 IFS Initial version 1 00 1 00 PLC Modbus RTU mode 1 30 1 00 Support fo...

Page 17: ...on the module digital wide range inputs or outputs 0 V 250 V AC DC DIP switches for HOLD RESET behavior of outputs Loop power function for passive sensors For a detailed description of the available...

Page 18: ...RAD IFS 18 198 PHOENIX CONTACT 105542_en_05 2 4 Application examples The Radioline system offers a wide range of application options...

Page 19: ...N rail 9 Metal foot catch for DIN rail fixing 10 4 1 4 2 Connection terminal blocks for RS 485 interface 11 5 1 5 2 5 3 Connection terminal blocks for RS 232 interface 12 6 1 6 2 6 3 Relay output with...

Page 20: ...in conjunction with 24 V DC devices Figure 3 3 Radioline connection station with up to 32 I O extension modules Mount the wireless module to the left and the I O extension modules only to the right of...

Page 21: ...urely The device is only mechanically secured via the DIN rail Connect the desired number of I O extension modules to the wireless module via the DIN rail connector In order to meet the requirements f...

Page 22: ...5 mm2 Insert the wire with ferrule into the corresponding connection terminal block Use a screwdriver to tighten the screw in the opening above the connection terminal block Tightening torque 0 6 Nm F...

Page 23: ...ns With a system power supply via the bus foot If DIN rail connectors are used you can use the MINI SYS PS 100 240AC 24DC 1 5 sys tem power supply Order No 2866983 Connect the system power supply usin...

Page 24: ...d loops must be taken into consideration Galvanic disturbances along the reference potential interfere with the useful signal and the shielding effect is reduced If several devices are connected to a...

Page 25: ...ICON plug in screw terminal block Figure 3 1 item 10 Make sure the signal assignment is correct Figure 3 9 RS 485 interface pin assignment Table 3 1 DIP switches 1 and 2 termination network DIP switch...

Page 26: ...are not sure whether the device to be connected is of DTE or DCE type you can also measure the voltage Measure the voltage between Tx and GND in the idle state Voltage of approximately 5 V DTE device...

Page 27: ...bles on page 171 Figure 3 12 Connecting the antenna Install the antenna outside the control cabinet or building Please also observe the installation instructions for the antenna as well as Section For...

Page 28: ...RAD IFS 28 198 PHOENIX CONTACT 105542_en_05...

Page 29: ...F band 4 2 Encryption Off Network structure Mesh Device type Repeater slave Blacklisting WLAN channel 6 Data rate of the wireless interface 125 kbps 9 6 kbps Receive preamplifier Enabled Transmission...

Page 30: ...button until the DAT LED flashes Reset via PSI CONF software In the device selection area select Wireless RAD 2400 IFS or Wireless RAD 868 IFS Select Local Device Select Set device to factory default...

Page 31: ...8 onwards 4 2 1 I O data mode Figure 4 1 I O data mode By default upon delivery all wireless modules are in I O data mode For simple I O to I O applications with extension modules you can easily set t...

Page 32: ...ERR DO4 DO3 DO2 DO1 OFF ON DIP 1 1 2 3 4 COM1 NO1 NC1 COM2 NO2 NC2 COM3 NO3 NC3 COM4 NO4 NC4 RAD AO4 IFS PWR DAT ERR 2 2 IO MAP OFF ON DIP 1 1 2 3 4 U1 U2 I1 I2 2 1 U3 U4 I3 I4 4 3 RAD 2400 IFS RAD I...

Page 33: ...e You can connect the I O extension modules to the controller directly via the integrated RS 232 and RS 485 interface by means of wireless communication In PLC Modbus RTU mode the master wireless modu...

Page 34: ...0 2 3 2 4 IO MAP DI1L DI1H DI1 DI2L DI2H DI2 DI3L DI3H DI3 DI4L DI4H DI4 5 1 5 2 5 3 Pwr Dat Err RAD DI4 IFS 3 3 2 2 4 3 3 2 4 1 0 2 P MAP IO M D DI1L DI1H DI1 DI2L DI DI2H 2H D DI2 DI DI3L DI3H DI3 D...

Page 35: ...configuration stick contains a preset frequency band RF band An RF band is a group of frequencies made up of individual frequencies from the entire frequency band Different RF bands use different fre...

Page 36: ...nector into the S PORT of the wireless module Press the SET button on the wireless module for one second Parameter read in is started Read in has been completed when the DAT LED lights up once The new...

Page 37: ...reless module for at least six seconds The four RSSI bar graph LEDs start a running light from bottom to top Insert the memory stick in the S PORT of the wireless module Parameter copying is started a...

Page 38: ...he wireless module for at least six seconds Parameter read in is started the DAT LED flashes The read in process has been completed once the DAT LED stops flashing The new parameters are activated Rem...

Page 39: ...Network Settings 4 6 2 Transmission power Observe the maximum permissible radiated transmission power at the antenna EIRP see Table 4 4 or Table 4 5 If necessary reduce the device transmission power...

Page 40: ...te obstacles such as walls or trees can be penetrated much better Please note however that the delay time increases when the data rate is reduced Adjust the data transmission rate of the wireless inte...

Page 41: ...Configuration and startup 105542_en_05 PHOENIX CONTACT 41 198 Figure 4 8 PSI CONF software Wizard Step 3 Figure 4 9 PSI CONF software setting the data transmission rate...

Page 42: ...fault upon delivery the receive preamplifier is activated The transmission power is set so that the devices can cover the greatest possible distances RAD 2400 IFS 18 dBm RAD 2400 IFS JP 20 dBm RAD 868...

Page 43: ...Under Individual Settings on the Allowed Parents tab you can define the wireless mod ules to which a connection may be established This setting is required for example when creating repeater chains Re...

Page 44: ...f No supply voltage On Supply voltage OK Off No communication Flashing Configuration mode On Cyclic data communication Off No error Flashing Slow 1 4 Hz Wireless module in I O data mode Double assignm...

Page 45: ...p Connection with good receive signal 1 5 V 2 V One yellow LED lights up Connection with weak receive signal 1 V 1 5 V Off Not connected configuration mode or overload1 1 By default upon delivery the...

Page 46: ...in write mode for the memory stick 16k 125k 250k RSSI voltage LED 3 70 dBm 65 dBm 60 dBm 2 5 V LED 2 80 dBm 75 dBm 70 dBm 2 0 V LED 1 90 dBm 85 dBm 80 dBm 1 5 V LINK LED LINK LINK LINK 1 0 V 1 2k 9 6...

Page 47: ...ce the DAT LED stops flashing RF link relay The RF link relay in the wireless module diagnoses the state of the wireless connection If the device is no longer receiving the data packets correctly the...

Page 48: ...veral wireless modules This is not possible for technical rea sons however This is why only the yellow bar graph LED lights up for the master You can read the RSSI values via the serial interface of t...

Page 49: ...esent the error message is reset Possible error messages Missing input module Missing output module Double assignment of I O MAP address Error on IFS bus Wireless connection interrupted RAD ID changed...

Page 50: ...s the status and the current values of the connected I O extension modules Figure 4 17 PSI CONF software Diagnostic I O Status The Serial Port tab displays the parameters currently set for the RS 232...

Page 51: ...d current values of the connected extension modules Click on Record under Diagnostic Select Network diagnose or I O diagnostics under Select the type of data to record Under Recording interval you can...

Page 52: ...DI3H DI4H DI3 DI4 RAD 2400 IFS RAD ID SPORT PWR DAT ERR RX TX 9 9 Reset D A D B RX CO1 TX CO2 GND NC1 24 V RSSI 0 V ANT RSSI RAD DOR4 IFS IO MAP PWR DAT ERR DO2 DO1 DI2 DI1 COM3 COM4 NO3 NO4 NC3 NC4...

Page 53: ...The following conditions must be met Addresses 1 99 maximum can be assigned for the extension modules in the entire wireless network Table 4 9 Assignment of input modules and output modules Input modu...

Page 54: ...ons in the network The I O MAP address of an input module may only appear once in the network The input and output data is saved in a Modbus memory map in the master wireless module You can read or wr...

Page 55: ...odule using the PSI CONF software In order to connect the wireless module to the PC use the RAD CABLE USB cable Order No 2903447 WARNING Explosion hazard when used in potentially explosive areas The U...

Page 56: ...he PSI CONF software Follow the software wizard Once you have performed all the steps in the wizard you can save the project and transfer it to the wireless modules Figure 5 2 PSI CONF software Wizard...

Page 57: ...ved by the wireless module is followed by a certain period of time where no further data is received the wireless module assumes that the frame has arrived in its en tirety The frame is then transmitt...

Page 58: ...cation is aborted you must increase the minimum pause time TFrameEnd between the in dividual characters of a telegram To adapt data transmission to other protocols you can adjust the TFrameEnd and TId...

Page 59: ...M2 NO1 NO2 NC1 NC2 0 1 RESET MRESET STOP RUN PROG X1 LNK ACT PRG 1 1 D TR 2 1 1 2 1 3 1 4 2 2 2 3 2 4 1 1 TxD TxD 2 1 1 2 1 3 1 4 2 2 2 3 2 4 1 1 2 1 1 2 1 3 1 4 2 2 2 3 2 4 1 1 2 1 1 2 1 3 1 4 2 2 2...

Page 60: ...he interface parameters Please note that the controller settings must match the settings of the wireless module You can monitor the Modbus connection between the controller and the wireless module via...

Page 61: ...1 5 2 5 3 DI1 DI2 DI3 DI4 3 1 3 2 3 3 4 1 4 2 4 3 4 1 4 2 4 3 RX TX 2 1 2 2 2 3 5 1 5 2 5 3 DI1 DI2 DI3 DI4 3 1 3 2 3 3 4 1 4 2 4 3 2 1 2 3 D A D B RX TX CO1 NO 4 1 4 2 4 3 D A D A D B B D B B RX RX T...

Page 62: ...RX CO1 TX CO2 GND NC1 24 V RSSI 0 V ANT RSSI IO MAP PWR DAT ERR DO2 DO1 DI2 DI1 OFF ON DIP 1 1 2 3 4 DI1L DI2L DI1H DI2H DI1 DI2 UL1 I1 I1 U1 I1 1 COM1 COM2 NO1 NO2 NC1 NC2 0 1 RESET MRESET STOP RUN P...

Page 63: ...5 interface you must set the interface parameters Please note that the controller settings must match the settings of the wireless module You can monitor the Modbus connection between the controller a...

Page 64: ...e door is a Modbus RTU slave the door opener is a digital out put Until now either two Modbus slaves and a wireless system were required or two sepa rate wireless systems for serial transmission and I...

Page 65: ...ngs Network Settings If the watchdog is triggered an action will be performed on the I O output modules You can set this behavior in the event of an error using the DIP switches on the front OFF RESET...

Page 66: ...range 4xxxx is already defined by the function code field Table 6 3 Supported Modbus function codes Code number Function code Description fc 03 Read Holding Register Read OUT process data address ran...

Page 67: ...d in the Modbus table but is no longer updated In the case of an output module the timeliness of data register value is set to 1 until the OUT process data has been written to the Modbus registers The...

Page 68: ...dividual extension modules show at what loca tion the I O data is stored in the Modbus memory map You can find a complete overview of the Modbus memory map from page 79 onwards The RSSI signal registe...

Page 69: ...e register value is 1 This is the case for example if the wireless connection or communication with an input module fails In this case the IN process data is re tained in the Modbus table but is no lo...

Page 70: ...then the register value is 1 This is the case for example if the wireless connection or communication with an input module fails In this case the IN process data is re tained in the Modbus table but i...

Page 71: ...ate then the register value is 1 If the process data has been written to one of the registers then the register value is 0 The register value then remains 0 for the entire operat ing time of the devic...

Page 72: ...14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 Y2 2 Y timeliness of data bit 8 If the data in the register is not up to date then the register value is 1 This is the case for example if the wireless co...

Page 73: ...able 6 13 RAD DI8 IFS module type and timeliness of data 30xx01 1 xx I O MAP address set using the white thumbwheel Module type and timeliness of data 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 Y...

Page 74: ...mode terminal point 2 x 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 Counter state DI1 high word 30xx4 DI7 32 bit pulse input pulse counter mode terminal point 5 x 15 14 13 12 11 10 09 08 07 06 05...

Page 75: ...imeliness of data 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 Y2 2 Y timeliness of data bit 8 If the data in the register is not up to date then the register value is 1 If the process data has bee...

Page 76: ...he process data has been written to one of the registers bit 8 in 40xx0 is set to 0 The value in register 40xx0 then remains 0 for the entire operating time of the device However in register 30xx0 bit...

Page 77: ...16 Table 6 16 RAD DAIO6 IFS module type and timeliness of data 30xx01 1 xx I O MAP address set using the white thumbwheel Module type and timeliness of data 15 14 13 12 11 10 09 08 07 06 05 04 03 02...

Page 78: ...30xx2 Analog input terminal point 3 x 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 AI1 30xx3 30xx9 Reserved 40xx1 Digital outputs 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 DO 2 DO 1 Terminal...

Page 79: ...8 Low byte 7 0 I O MAP High byte 15 8 Low byte 7 0 30 xx 0 Timeliness of data Module type ID 40 xx 0 Timeliness of data Module type ID X X X X X X X X X X X X X X X X X X 30 xx 1 DI4 DI1 40 xx 1 DO4 D...

Page 80: ...X X 30xx2 30xx9 reserved 40xx2 40xx9 reserved RAD AI4 IFS RAD AO4 IFS I O MAP High byte 15 8 Low byte 7 0 I O MAP High byte 15 8 Low byte 7 0 30 xx 0 Timeliness of data Module type ID 40 xx 0 Timelin...

Page 81: ...MAP High byte 15 8 Low byte 7 0 30 xx 0 Timeliness of data Module type ID X X X X X X X X X 30 xx 1 Reserved 30 xx 2 T1 X X X X X X X X X X X X X X X X 30 xx 3 T2 X X X X X X X X X X X X X X X X 30 x...

Page 82: ...nected from the DIN rail connector If no error is present on the IFS bus the register value is 0 Bits 9 15 are reserved Values 255 indicate the RSSI value in dBm Value 255 means that the RSSI value is...

Page 83: ...1770 6000 4 mA 4 mA 7530 30000 20 mA 20 mA 7F00 32512 21 67 mA 21 67 mA 8001 Overrange 21 67 mA 21 67 mA 8002 Open circuit 3 2 mA 8080 Underrange 0 mA Table 6 19 Representation of RAD AO4 IFS analog...

Page 84: ...m devices into a fully fledged part of your control system The Radioline function blocks are suitable for PC Worx STEP 7 and TIA Portal Thanks to modern wireless technology I O signals from distribute...

Page 85: ...act controllers Figure 6 9 I O integration in PC Worx Required components Radioline front module Radioline I O extension modules Inline or Axioline controllers Inline or Axioline RS 485 communication...

Page 86: ...ion in TIA Portal or STEP 7 Required components Radioline front module Radioline I O extension modules Inline or Axioline bus coupler Inline or Axioline RS 485 communication module S7 3xx S7 12xx S7 1...

Page 87: ...on 1 3 1 3 2 3 3 Analog input 2 for 2 3 4 wire measuring transducers 2 2 1 2 2 2 3 Analog input 1 for 2 3 4 wire measuring transducers 3 DIP switches for configuring the analog inputs 0 mA 20 mA 4 mA...

Page 88: ...s possible to detect an open circuit Figure 7 3 DIP switches of the RAD AI4 IFS Table 7 1 DIP switches of the RAD AI4 IFS DIP switch Setting Input signal 1 2 3 4 Analog IN1 0 mA 20 mA OFF 4 mA 20 mA O...

Page 89: ...the supply voltage DAT LED The green DAT LED indicates the status of bus communication ERR LED The red ERR LED indicates the error status Off No supply voltage On Supply voltage OK Off No communicatio...

Page 90: ...data in PLC Modbus RTU mode The process image of the I O extension module consists of six data words For additional information please refer to Section RAD AI4 IFS process data on page 69 Table 7 2 S...

Page 91: ...00 resistance temperature detectors can be connected to the RAD PT100 4 IFS I O extension module The temperature detectors change their resistance according to the temperature The RAD PT100 4 IFS acqu...

Page 92: ...and x 3 Figure 7 5 2 wire connection technology 3 wire connection technology With 3 wire connection technology the temperature related voltage is measured several times Corresponding calculations add...

Page 93: ...tion of two cable resistances Figure 7 7 4 wire connection technology 7 2 2 Measuring errors when using 2 wire connection technology Figure 7 8 Systematic temperature measuring error T depending on ca...

Page 94: ...ance You can calculate the cable resistance as follows Since there are two cable resistances in the measuring system the value must be doubled Using the average temperature coefficient 0 385 K for Pt1...

Page 95: ...r setting the I O MAP address 4 Connection option for DIN rail connector 5 DIN rail 6 Metal foot catch for DIN rail fixing 7 4 1 4 2 4 3 Pt100 input 3 for 2 and 3 wire sensors 8 5 1 5 2 5 3 Pt100 inpu...

Page 96: ...n bridge is required between terminal blocks x 2 and x 3 In this case the measuring accuracy is reduced see Measuring errors when using 2 wire connection technology on page 93 2 1 2 3 I1 I1 3 wire 2 2...

Page 97: ...FS PWR LED The green PWR LED indicates the status of the supply voltage DAT LED The green DAT LED indicates the status of bus communication ERR LED The red ERR LED indicates the error status Off No su...

Page 98: ...process data on page 70 7 3 RAD AO4 IFS analog extension module with four outputs The RAD AO4 IFS analog I O extension module can output up to four input signals with 0 4 mA 20 mA All outputs are elec...

Page 99: ...I O MAP address 5 Connection option for DIN rail connector 6 DIN rail 7 Metal foot catch for DIN rail fixing 8 4 1 4 2 4 3 Analog output 3 either current or voltage 9 5 1 5 2 5 3 Analog output 4 eith...

Page 100: ...switch set tings will be applied immediately RESET output value is set to 0 HOLD hold the last valid output value Figure 7 16 DIP switches of the RAD AO4 IFS Table 7 5 DIP switches of the RAD AO4 IFS...

Page 101: ...LED indicates the error status e g if a corresponding input module has not been found Off No supply voltage On Supply voltage OK Off No communication Flashing Configuration and addressing mode On Cyc...

Page 102: ...tal I O extension module can process up to four input signals The dig ital inputs process the following voltages 0 V 50 V AC DC at the low voltage input 0 V 250 V AC DC at the high voltage input All i...

Page 103: ...etal foot catch for DIN rail fixing 7 5 1 5 2 5 3 Digital input as wide range input 8 6 1 6 2 6 3 Digital input as wide range input 9 Status LEDs for digital inputs DI1 DI4 10 ERR status LED red commu...

Page 104: ...n ERR LED The red ERR LED indicates the error status e g if a corresponding output module has not been found DI1 DI4 The yellow DI1 DI4 LEDs indicate the state of the digital inputs Off No supply volt...

Page 105: ...k 7 4 5 Process data in PLC Modbus RTU mode The process image of the I O extension module consists of two data words For additional information please refer to Section RAD DI4 IFS process data on page...

Page 106: ...block Designation 1 3 1 3 2 3 3 Digital inputs 3 4 2 2 1 2 2 2 3 Digital inputs 1 2 DI1 pulse input 1 3 White thumbwheel for setting the I O MAP address 4 DIP switches for switching between static mod...

Page 107: ...e activated 0 V 30 5 V DC voltage In pulse counter mode pulse inputs DI1 and DI7 are activated 0 Hz 100 Hz pulses Figure 7 23 DIP switches of the RAD DI8 IFS The pulse counter function is only availab...

Page 108: ...the counter state manually Via power up Disconnect the device power supply and then reconnect the voltage Via Modbus RTU register Reset the counter states via Modbus RTU as follows DI1 bit 0 1 registe...

Page 109: ...dicates the status of the supply voltage DAT LED The green DAT LED indicates the status of bus communication ERR LED The red ERR LED indicates the error status Off No supply voltage On Supply voltage...

Page 110: ...the I O extension module consists of eight data words For additional information please refer to Section RAD DI8 IFS process data on page 73 Off No error Flashing Mode switched using DIP switch 1 but...

Page 111: ...ock Designation 1 2 1 2 2 2 3 Relay output 2 with floating changeover contact 2 1 1 1 2 1 3 Relay output 1 with floating changeover contact 3 DIP switches for configuring the output behavior of the re...

Page 112: ...on of the wireless connection Any changes to the DIP switch set tings will be applied immediately RESET output value is set to 0 HOLD hold the last output value Figure 7 27 DIP switches of the RAD DOR...

Page 113: ...green DAT LED indicates the status of bus communication Table 7 10 DIP switches of the RAD DOR4 IFS DIP switch Setting Output signal 1 2 3 4 Digital OUT1 RESET OFF HOLD ON Digital OUT2 RESET OFF HOLD...

Page 114: ...dule consists of two data words For additional information on the process data please refer to Section RAD DOR4 IFS process data on page 75 Off No error Flashing Slow 1 4 Hz I O MAP address changed Fa...

Page 115: ...ged in two groups of four outputs each with a common supply The two output groups are electrically isolated from one another from the supply voltage and from the electronics Since output groups DO1 DO...

Page 116: ...nector 7 DIN rail 8 Metal foot catch for DIN rail fixing 9 4 1 4 2 4 3 Transistor outputs 5 6 10 5 1 5 2 5 3 Transistor outputs 7 8 11 6 1 6 2 6 3 Supply voltage for outputs 5 8 12 Status LEDs of tran...

Page 117: ...he outputs in the event of an error e g interruption of the wireless connection Any changes to the DIP switch set tings will be applied immediately RESET output value is set to 0 HOLD hold the last ou...

Page 118: ...age DAT LED The green DAT LED indicates the status of bus communication Table 7 12 DIP switches of the RAD DO8 IFS DIP switch Setting Output signal 1 2 3 4 Digital OUT 1 4 RESET OFF n c n c Digital OU...

Page 119: ...s in the entire wireless network Off No error Flashing Wireless module in I O data mode Missing input module No bus communication Wireless module in PLC Modbus RTU mode No Modbus communication safe st...

Page 120: ...tage input and volt ages of 0 V 250 V AC DC at the high voltage input Two digital outputs The digital outputs are designed as floating relay contacts changeover contacts The switching capacity is 2 A...

Page 121: ...rail 8 Metal foot catch for DIN rail fixing 9 4 1 4 2 4 3 Analog output either current or voltage 10 5 1 5 2 5 3 Relay output with floating changeover contact 11 6 1 6 2 6 3 Relay output with floating...

Page 122: ...s will be applied immediately Analog output RESET output value is set to 0 HOLD hold the last output value Digital outputs RESET relay drops out HOLD hold the last valid state Figure 7 35 DIP switches...

Page 123: ...LED indicates the status of the supply voltage DAT LED The green DAT LED indicates the status of bus communication Table 7 14 DIP switches of the RAD DAIO6 IFS DIP switch Setting Output signal 1 2 3...

Page 124: ...ess image of the I O extension module consists of six data words For additional information please refer to Section RAD DAIO6 IFS process data on page 77 Off No error Flashing Slow 1 4 Hz I O MAP addr...

Page 125: ...ce Among other things the delay time depends on the following factors Frequency band used 2 4 GHz or 868 MHz the higher the frequency the lower the delay time Utilization of the frequency band The mor...

Page 126: ...rface kbps Data rate of the wireless interface kbps Typical delay time Telegram length1 2 4 GHz I O data mode 250 150 ms 49 bytes 125 200 ms 16 500 ms Serial data mode 19 2 250 20 ms 125 25 ms 16 120...

Page 127: ...ounter mode the master wireless module maintains a central 32 bit Modbus reg ister with the counter state of the relevant pulse input The Modbus register can be read and written by any PLC via Modbus...

Page 128: ...on and authentication Trusted Wireless 2 0 is a proprietary technology The protocol has not been published Therefore it is better protected against attacks In addition two security mechanisms have bee...

Page 129: ...equency band In the 868 MHz fre quency band the transmission power may reach 27 dBm 500 mW Due to the higher transmission power in the 868 MHz frequency band longer ranges can also be achieved Duty cy...

Page 130: ...Bee use centralized network management That means that all messages pass through a central manager which can lead to a signifi cant volume of wireless network traffic Trusted Wireless 2 0 on the other...

Page 131: ...er the air OTA data rate Figure 8 5 RF bands in the 868 MHz wireless system Point to point connection star network I O serial PLC Modbus RTU mode Mesh network 250 kbps 125 kbps 16 kbps 8 RF bands freq...

Page 132: ...of a repeater or higher mast When evaluating the data a system calculation can be carried out to determine whether the wireless path is theoretically possible A calculation example can be found from p...

Page 133: ...em and the required range In addition the different antenna types are suitable for the following areas of application Omnidirectional antenna Numerous devices in different directions e g in mesh netwo...

Page 134: ...as Note the polarization of the antenna Most systems use a vertically polarized omnidirec tional antenna at the master station The partner antennas must therefore also be polarized vertically Vertical...

Page 135: ...s horizontally and vertically The signals of the various wireless paths will therefore be decoupled Figure 8 7 Decoupling of wireless paths due to directivity and different polarization levels Table 8...

Page 136: ...n outdoor applications use RAD TAPE SV 19 3 vulcanizing sealing tape Order No 2903182 to protect adapters cable connections etc Run the antenna cable inside the mast or fasten it to the outside of the...

Page 137: ...ation of wireless modules and accessories Keep the connection between the wireless module and the antenna as short as possible Every extension or adapter cable pigtail will cause higher attenuation Yo...

Page 138: ...a Connection Order No Gain Remark 2 4 GHz omnidirectional antenna RAD ISM 2400 ANT OMNI 2 1 RSMA RSMA m 2701362 2 1 dBi 2 1 dBi 2 1 dB 1 5 m cable RG316 RAD ISM 2400 ANT VAN 3 0 RSMA RSMA m 2701358 3...

Page 139: ...4 GHz Attenuation at 868 MHz 5 m 54 dB 10 m 60 dB 20 m 66 dB 30 m 69 5 dB 50 m 74 dB 100 m 80 dB 71 2 dB 110 m 80 8 dB 120 m 81 6 dB 150 m 83 5 dB 200 m 86 dB 77 2 dB 250 m 88 dB 300 m 89 5 dB 80 7 d...

Page 140: ...tennas in km The free space attenuation is later included in the system calculation see Section Equiva lent isotropically radiated power EIRP on page 147 9000 m 110 3 dB 10 km 111 2 dB 11 km 112 dB 12...

Page 141: ...r a tree with leaves will scatter the signals considerably The leaf surfaces disperse the wireless sig nal in many different directions Figure 8 9 Dispersion on a rough surface Diffraction Diffraction...

Page 142: ...lls Elevator shafts and staircases Each material has a different degree of attenuation However the following typical values provide a rough guide Figure 8 12 Reduction of radio waves when penetrating...

Page 143: ...ot no direct radio waves can reach it It can only receive reflections or diffracted waves Figure 8 14 Radio dead spot RAD 2400 IFS RAD ID Reset 24 V 0 V RSSI RSSI ANT SPORT 0 1 Pwr Dat Err RX TX D A D...

Page 144: ...here should be a line of sight between the antennas espe cially when covering large distances In order to stay within the Fresnel zone it might be necessary to install the antennas at a height of a fe...

Page 145: ...zone for 2 4 GHz and d 3000 m r 9 68 m Result the radius of the Fresnel zone is 9 68 m at a wavelength of 0 125 m 2 4 GHz and a distance of 3000 m between the antennas Table 8 8 Radius of the Fresnel...

Page 146: ...at 2 4 GHz Antenna 2 4 GHz Data rate of the wireless interface Range Inside buildings Omnidirectional antenna 2 dBi 250 kbps 50 m 100 m 125 kbps 100 m 200 m Outside buildings with a free line of sigh...

Page 147: ...following maximum EIRP for legal reasons For 2 4 GHz Maximum of 20 dBm outside Europe Maximum of 19 dBm in Europe depending on the set transmission rate For 868 MHz Maximum of 27 dBm If the maximum E...

Page 148: ...ee space attenuation dB gain of the receiving antenna dBi attenuation of the antenna cable at the receiver dBm System reserve receiver sensitivity dBm incoming power for the receiver dBm recommended s...

Page 149: ...r applications The bush illustrated below is 2 m wide and has an attenuation of approximately 15 dB at 2 4 GHz At 868 MHz the attenuation is around 8 dB Figure 8 18 Bush with an attenuation of approxi...

Page 150: ...RAD IFS 150 198 PHOENIX CONTACT 105542_en_05...

Page 151: ...he signal strength always relates to the directly connected overlap ping wireless module The RSSI indicator is a voltage output in the range from 0 V DC 3 V DC The higher the voltage the better the wi...

Page 152: ...data mode Check whether the I O extension module is properly snapped onto the DIN rail connector and whether it is connected to the wireless module Check the operating mode of the wireless module usin...

Page 153: ...me ters have the same settings on all wireless modules operating mode network ID RF band data rate of the wireless interface en cryption network type from page 38 onwards Reset the wireless module to...

Page 154: ...MAP address in a network The I O MAP address of an input module may only appear once in the network Use the white thumbwheel to set different I O MAP addresses Missing input module Example an output...

Page 155: ...the Modbus RTU controller and the master wireless module using RAD ID 01 Check the wiring of the RS 232 RS 485 connections on the wireless modules Check the serial interface settings baud rate parity...

Page 156: ...on the wireless module In I O data mode ERR flash ing fast 2 8 Hz Missing input module Example an output module is not assigned the corresponding input module with the same I O MAP address Check wheth...

Page 157: ...using a terminal program e g HyperTerminal The characters are echoed back to the terminal program To carry out a loopback test proceed as follows Close all programs on your PC including the PSI CONF...

Page 158: ...int 5 2 TX cable of the RS 232 interface This returns the transmitted characters and they appear twice on the HyperTerminal screen The screen remains blank if the check was not successful Monitor the...

Page 159: ...adioline wireless system up to 99 stations range of up to 1 2 km on in house copper ca bles RAD RS485 IFS 2702184 1 Extension modules Type Order No Pcs Pkt I O extension module 4 analog current inputs...

Page 160: ...D 2 4 GHz RF band 3 2 4 GHz RF band 5 2 4 GHz RF band 7 868 MHz RF band 1 RAD CONF RF3 RAD CONF RF5 RAD CONF RF7 RAD 868 CONF RF1 2902814 2902815 2902816 2702197 1 1 1 1 2 4 GHz antennas Type Order No...

Page 161: ...ntenna with protection against vandal ism 868 MHz gain 2 5 dBi polarization linear vertical opening angle h v 360 55 degree of protection IP67 shock resistance IK08 connection N female for control cab...

Page 162: ...xible attenuation 0 3 0 5 0 8 dB at 0 9 2 4 5 8 GHz connection 2 x N male cable length 0 5 m FL LCX PIG EF142 N N 2700677 1 Attachment plug with LAMBDA 4 technology as surge protection for coaxial sig...

Page 163: ...90 angled RAD ADP RSMA M RSMA F 90 2904790 1 Antenna cables and adapters Type Order No Pcs Pkt Energy supply Type Order No Pcs Pkt Solar system for worldwide use consisting of a solar panel prewired...

Page 164: ...stand alone 6 A at 24 V DC with DIN rail connector at full capacity Transient surge protection Yes System limits RAD 2400 IFS RAD 868 IFS Wireless module Number of devices supported Number of possible...

Page 165: ...kbps 111 dBm 19 2 kbps 104 dBm 60 kbps 103 dBm 120 kbps Transmission power 20 dBm outside Europe can be set via software 19 dBm Europe can be set via software depends on the data rate 18 dBm default...

Page 166: ...onductor cross section flexible 0 2 mm 2 5 mm Conductor cross section AWG kcmil 24 14 Stripping length 7 mm Tightening torque 0 6 Nm Status indicator Status indicator Green LED supply voltage PWR Gree...

Page 167: ...2014 53 EU No ATEX II 3 G Ex nA nC IIC T4 Gc IBExU 15 ATEX B008 X No IECEx Ex nA nC IIC T4 Gc IECEx IBE 13 0019X No FCC FCC directive part 15 247 No No ISC ISC directive RSS 210 No No IFT Mexico IFT...

Page 168: ...terference EN 61000 4 5 Frequency range 0 15 MHz 80 MHz Voltage 10 V Comment Criterion A Noise emission according to EN 61000 6 4 RAD 2400 IFS and RAD 868 IFS Emitted radio interference according to E...

Page 169: ...two of the four possible digital inputs and outputs Operating conditions for the extended temperature range 55 C 70 C No function restrictions for the extended temperature range if you keep a minimum...

Page 170: ...en_05 RAD DOR4 IFS 2901536 Maximum switching current 1 A per channel RAD AI4 IFS 2901537 Make sure that no more than 40 mA in total is drawn from loop power outputs PWR1 PWR4 RAD AO4 IFS 2901538 Only...

Page 171: ...antenna outside the control cabinet or building Observe the installation instructions for the antenna and the Section For your safety on page 7 For information on the transmission power please refer...

Page 172: ...IFS RAD ID Reset 24 V 0 V RSSI RSSI ANT SPORT 0 2 Pwr Dat Err RX TX D A D B GND RX CO1 NC1 CO2 TX 1 Item Product Description Connection Order No 1 RAD ISM 2400 ANT VAN 3 0 RSMA Omnidirectional antenna...

Page 173: ...0 V RSSI RSSI ANT SPORT 0 2 Pwr Dat Err RX TX D A D B GND RX CO1 NC1 CO2 TX 1 2 Item Product Description Connection Order No 1 ANT OMNI 2459 02 Omnidirectional antenna 2 4 GHz 5 GHz 2 5 5 dBi gain lin...

Page 174: ...ction Order No 1 RAD ISM 2400 ANT OMNI 6 0 Omnidirectional antenna 2 4 GHz 6 dBi gain linear vertical polarization h v 360 30 open ing angle IP67 protection seawater resistant N female 2885919 2 RAD P...

Page 175: ...sistant N female 2885919 2 opt RAD CAB EF393 3M Antenna cable 3 m length 50 impedance N male N male 2867649 Alternative RAD CAB EF393 5M Antenna cable 5 m length N male N male 2867652 RAD CAB EF393 10...

Page 176: ...t RAD CAB EF393 3M Antenna cable 3 m length 50 impedance N male N male 2867649 Alternative RAD CAB EF393 5M Antenna cable 5 m length N male N male 2867652 RAD CAB EF393 10M Antenna cable 10 m length 2...

Page 177: ...female 2867885 2 opt RAD CAB EF393 3M Antenna cable 3 m length 50 impedance N male N male 2867649 Alternative RAD CAB EF393 5M Antenna cable 5 m length N male N male 2867652 RAD CAB EF393 10M Antenna...

Page 178: ...nna 868 MHz 4 dBi lin ear vertical h v 360 30 opening angle IP67 seawater resistant including mounting bracket and mast clips for 30 mm 45 mm diameter stainless steel ATEX IECEx approval N female 2702...

Page 179: ...length 2903266 RAD PIG RSMA N 5 Antenna cable 5 m length 2702140 Item Product Description Connection Order No RAD 2400 IFS RAD ID Reset 24 V 0 V RSSI RSSI ANT SPORT 0 1 Pwr Dat Err RX TX D A D B GND...

Page 180: ...34 3 opt CN LAMBDA 4 5 9 BB Attachment plug with LAMBDA 4 technology as surge protection for coaxial signal interfaces N female N female 2838490 4 RAD PIG RSMA N 0 5 Antenna cable 0 5 m length 50 impe...

Page 181: ...ion Connection Order No 1 ANT DIR 2459 01 Directional antenna 2 4 GHz 5 GHz 9 dBi gain linear vertical polarization h v 75 55 opening angle for 2 4 GHz IP67 protection N female 2701186 Alternative ANT...

Page 182: ...IG RSMA N 3 Antenna cable 3 m length 2903266 RAD PIG RSMA N 5 Antenna cable 5 m length 2702140 Item Product Description Connection Order No WARNING Explosion hazard when used in potentially explosive...

Page 183: ...rnative RAD CAB EF393 5M Antenna cable 5 m length N male N male 2867652 RAD CAB EF393 10M Antenna cable 10 m length 2867665 RAD CAB EF393 15M Antenna cable 15 m length 2885634 7 ANT DIR 2459 01 Direct...

Page 184: ...vices and terminal blocks Power supply MINI SYS PS 100 240AC 24DC 1 5 1500 mA Load Wireless module 65 mA RAD DAIO6 IFS 95 mA RAD DI4 IFS 11 mA RAD DOR4 IFS 55 mA RAD DI8 IFS 18 mA RAD DO8 IFS 22 mA RA...

Page 185: ...C Modbus RTU dual mode 34 Figure 4 6 Configuration using the configuration stick 36 Figure 4 7 PSI CONF software Network Settings 39 Figure 4 8 PSI CONF software Wizard Step 3 41 Figure 4 9 PSI CONF s...

Page 186: ...blocks for Radioline 84 Figure 6 9 I O integration in PC Worx 85 Figure 6 10 I O integration in TIA Portal or STEP 7 86 Figure 7 1 RAD AI4 IFS structure 87 Figure 7 2 Basic circuit diagram for the RA...

Page 187: ...6 IFS 122 Figure 7 35 DIP switches of the RAD DAIO6 IFS 122 Figure 7 36 Diagnostics LEDs of the RAD DAIO6 IFS 123 Figure 8 1 Penetration of obstacles at different frequencies 129 Figure 8 2 Point to p...

Page 188: ...re A 4 Omnidirectional antenna 6 dBi without surge protection 174 Figure A 5 Omnidirectional antenna 6 dBi with surge protection 175 Figure A 6 Directional antenna 9 dBi with outdoor surge protection...

Page 189: ...des 66 Table 6 4 Module type and timeliness of data 67 Table 6 5 Module type IDs 67 Table 6 6 Setting the white thumbwheel for register 30010 read 68 Table 6 7 RSSI voltage 2 4 GHz 68 Table 6 8 RSSI v...

Page 190: ...O8 IFS 118 Table 7 13 Setting the I O MAP address for the RAD DO8 IFS 119 Table 7 14 DIP switches of the RAD DAIO6 IFS 123 Table 7 15 Setting the I O MAP address for the RAD DAIO6 IFS 124 Table 8 1 Ty...

Page 191: ...48 Point to point connection 48 Blacklisting 128 Brief description 15 C Cable 133 171 Checking the location 132 Circuit diagram RAD AI4 IFS 88 RAD AO4 IFS 99 RAD DAIO 6 IFS 122 RAD DI4 IFS 103 RAD DI...

Page 192: ...module Combinations 52 Product description 87 F Factory settings 29 Fault message contact 47 FCC 13 FHSS Frequency Hopping Spread Spectrum See Frequency hopping method Firmware update 30 Firmware ver...

Page 193: ...100 value 84 Pulse counter mode 107 Pulse transmission 127 R RAD AI4 IFS 87 RAD AO4 IFS 98 RAD DAIO6 IFS 120 RAD DI4 IFS 102 RAD DI8 IFS 106 RAD DO8 IFS 115 RAD DOR4 IFS 111 Radiated power See Equival...

Page 194: ...ystem power supply 23 T T BUS See DIN rail connector Technical data 159 Temperature input 91 Temperature measuring error See Measuring error Temperature range 169 Temperature sensor 2 wire sensor 92 3...

Page 195: ...Index 105542_en_05 PHOENIX CONTACT 195 198...

Page 196: ...RAD IFS 196 198 PHOENIX CONTACT 105542_en_05...

Page 197: ...products in your specific application in particular with regard to observing the applicable standards and regulations All information made available in the technical data is supplied without any acco...

Page 198: ...ation It can be downloaded at phoenixcontact net products Subsidiaries If there are any problems that cannot be solved using the documentation please contact your Phoenix Contact subsidiary Subsidiary...

Reviews: