AXL F BK PN
105731_en_01
PHOENIX CONTACT
5
Interface Service
Number
1
Connection method
Micro USB type B
System limits
Number of supported devices
max. 63 (per station)
NOTE: Electronics may be damaged when overloaded
Observe the logic current consumption of each device when configuring an Axioline
F station. It is specified in every module-specific data
sheet. The current consumption can differ depending on the individual module. The permissible number of devices that can be connected
therefore depends on the specific station structure.
Protocols supported
Protocols supported
PROFINET, FTP, TFTP, PTCP, LLDP, SNMP, MRP, DDI, Boot
P
Supply of the bus coupler
Supply of communications power U
L
24 V DC
Maximum permissible voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current supply at U
Bus
2 A
Current consumption from U
L
typ. 105 mA (without I/Os and U
L
= 24 V)
max. 570 mA (with 2
A at U
Bus
for the I/Os and U
L
= 24 V)
Power consumption at U
L
typ. 2.5 W (without I/Os)
max. 13.7 W (with 2
A load at U
Bus
for the I/Os)
NOTE: Electronics may be damaged when overloaded
Provide external fuses for the 24 V U
L
area. The power supply unit must be able to supply four times the nominal current of the external fuse
to ensure that it blows in the event of an error.
Error messages to the higher level control or computer system
None
Mechanical tests
Vibration resistance in acc. with EN
60068-2-6/IEC
60068-2-6
5g
Shock in acc. with EN
60068-2-27/IEC
60068-2-27
30g, 11 ms period, half-sine shock pulse
Continuous shock according to EN
60068-2-27/IEC
60068-2-27
10g
Conformance with EMC Directive 2004/108/EC
Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN
61000
-
4
-
2/IEC
61000
-
4
-
2
Criterion B; 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN
61000
-
4
-
3/IEC
61000
-
4
-
3
Criterion A; Field intensity: 10 V/m
Fast transients (burst) EN
61000
-
4
-
4/IEC
61000
-
4
-
4
Criterion B, 2
kV
Transient surge voltage (surge) EN
61000
-
4
-
5/IEC
61000
-
4
-
5
Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); field-
bus cable shield: ±1 kV
Conducted interference EN
61000
-
4
-
6/IEC
61000
-
4
-
6
Criterion A; Test voltage 10 V
Noise emission test according to EN 61000-6-3
Radio interference properties EN 55022
Class B
Approvals
For the latest approvals, please visit phoenixcontact.net/products.