2.3.2
Grounding
The grounding is performed - depending on the type of device - with a slip-on sleeve (noise-
less ground / functional earth ground) or a ring cable lug (protective ground).
1.
Strip approx. 5 mm (0.197") off the wires.
2.
Fit the stripped wires - depending on the type of device - with a slip-on sleeve or a ring
cable lug.
3.
Plug the slip-on sleeve on the flat tab or mount the ring cable lug with the nut to the
threaded bolt.
Figure 2-33
Noiseless ground / protective ground
NOTICE: Damage
A separate copper conductor must always be provided for the grounding. The conductor
must have a minimum cross-section of 1.5 mm² (16 AWG) and must be kept as short as
possible.
You must adhere to a maximum torque of 1 Nm at an protective grounding on the
threaded bolt.