Step 3: DSL line configura-
tion
The line already has a name (DSL line 1, etc.). You can assign a new name, e.g. "Path via
hall A". The name can contain 255 characters including special characters.
In the case of the point-to-point wizard, you can specify under "DSL line arrangement"
whether it is a 2-wire or 4-wire line. In the case of the line structure wizard, only 2-wire lines
are configured.
The DSL data rate can be automatically determined or you can set it manually:
–
Automatic data rate:
You can set the noise immunity for the link establishment using
the slider. The more the slider is moved to "green", the higher the immunity that is tak-
en into account and the lower the DSL data rate. (see also page 23). The automati-
cally determined data rate remains fixed until an SHDSL connection abort. The
SHDSL data rate is determined again when the SHDSL connection is re-established.
It may deviate from the previous data rate. In the case of extremely long lines that are
susceptible to interference, only data rates below 192 kbps may be possible. In this
case, automatic data rate detection will not work and you have to specify the data rate
manually.
–
Manual setting of the data rate:
Enter a fixed data rate. The lower the data rate, the
more robust is the connection. However, it does not normally make sense to use a
rate of less than 144 kbps. The slider control has no influence.
Configuration >> Point-to-point wizard or line structure wizard or ring structure wizard [...]
Summary of Contents for 2313643
Page 16: ...PSI MODEM SHDSL ETH TC ETH EXTENDER 16 PHOENIX CONTACT 104273_en_01...
Page 20: ...PSI MODEM SHDSL ETH TC ETH EXTENDER 20 PHOENIX CONTACT 104273_en_01...
Page 50: ...PSI MODEM SHDSL ETH 50 PHOENIX CONTACT 104273_en_01...
Page 78: ...PSI MODEM SHDSL ETH TC ETH EXTENDER 78 PHOENIX CONTACT 104273_en_01...
Page 94: ...PSI MODEM SHDSL ETH TC ETH EXTENDER 94 PHOENIX CONTACT 104273_en_01...