Ensure all circuit breakers are open / disabled before wiring the units so that there is no voltage on all battery, AC and 
PV wires. 

 

AC Input & Output Connections 

Regarding AC input and output, please also follow the same principle. Use the wiring cross-section 

and circuit breaker as defined for each individual unit, then attach those wires to bus bars. The bus bars from the AC 

input are then connected to the AC source, the bus bars from the AC output are connected to the distribution panel 

and loads. 

 

Battery Connections 

Make sure to use a separate DC fuse or circuit breaker for each unit. Instead of connecting each unit to the battery, 

connect each positive battery cable to a bus bar, and each negative battery cable to a second bus bar. These bus bars 

are then connected to the battery terminals. The cross-section of the bus bars, and the cables from the bus bars to the 

battery  terminals  should  equal  the  recommended  battery  cable  cross-section  per  unit,  times  the  number  of  units 

connected to it. 

All inverters must share the same battery bank. Otherwise, the inverters will go into fault mode. 

Please install at least a breaker at the battery terminals and AC input of every individual Any -Grid 

unit.  This  will  ensure  each  unit  can  be  securely  disconnected  during  maintenance  and  fully  protected  from  over-

current of battery or AC input. Use the breaker ratings as described in the chapters 

“Battery Connection”

 and 

“AC Input 

and AC Output Connection”

 of the user manual. 

 

 

 

 

 

 

 

 

 

5.0

 

  Liability Exclusion 

The manufacturer shall not be liable for damages, especially on the battery, caused by use other than as intended or 
as mentioned in this document or if the recommendations of the battery manufacturer are neglected. The 
manufacturer shall not be liable if there has been service or repair carried out by any unauthorized person, unusual 
use, wrong installation, or incorrect system design. 

 

 

 

 