Figure 3 

STEP 3 (see figure 3) 

 

Remove desired knockouts for junction box or toggle bolt mounting.  Also remove the 

larger rectangular knockout for routing of AC leads unless using the conduit knockout found on 
top of the housing.  Mount unit to wall or ceiling using fasteners supplied with junction box or 
mount to wall using toggle bolts (not provided).  Pull AC and remote lamp connectors through 
rectangular knockout and reconnect to matching wire harnesses as shown in step two.  Reinstall 
the battery and connect the battery quick disconnect.  Re-secure the Velcro battery strap to secure 
the battery in place.  If MR-16 type lamps have been specified, they have been shipped in small 
individual cartons inside the larger shipping carton.  They are installed by press fitting into the 
ceramic lamp base inside each lamp head.  Energize AC supply branch circuit and refer to page 5 
for operating instructions. 

No rigid conduit – Flexible conduit only 

Summary of Contents for Symmetry Series

Page 1: ...o not use this equipment for other than intended use Do not let supply cords touch hot surfaces Do not mount near gas or electric heaters Caution Halogen cycle lamp s are used in this equipment To avoid shattering Do not operate lamp in excess of rated voltage protect lamp against abrasion and scratches and against liquids when lamp is operating dispose of lamp with care Halogen cycle lamps operat...

Page 2: ...his purpose can be found under the lenses These keyhole slots will accommodate 6 toggle bolts Refer to the sketch above for instructions on removing the lenses Figure 2 STEP 2 see figure 2 Locate 4 pole connector attached to transformer inside unit Remove 6 long extension cable and wire to AC supply as shown Unused black or blue lead must be insulated to prevent shorting If your unit has battery c...

Page 3: ... Mount unit to wall or ceiling using fasteners supplied with junction box or mount to wall using toggle bolts not provided Pull AC and remote lamp connectors through rectangular knockout and reconnect to matching wire harnesses as shown in step two Reinstall the battery and connect the battery quick disconnect Re secure the Velcro battery strap to secure the battery in place If MR 16 type lamps ha...

Page 4: ... covers as shown in step 1 Lamp heads may be aimed by grasping them at the base and rotating them to aim at the desired location Lamp head only rotates approximately 135 which is enough to aim in any direction whether mounted on wall or ceiling AC FUSE AND AC OR DC DISCONNECT SWITCH OPTIONS If ordered these options can be found under the right lamp head lens TAMPERPROOFING If ordered install this ...

Page 5: ...manually initiated diagnostic test Red LED indicator Single Flash battery fault Two Flashes lamp failure light bar failure EXIT signs Three Flashes charger fault Four Flashes transfer fault If more than one fault condition is present simultaneously the red LED will flash the indication pattern for each fault independently then repeat the cycle Pushbutton Test Switch Long Press longer than 0 5sec t...

Page 6: ...ion 200 Franklin Square Drive Somerset NJ 08873 USA Phone 855 486 2216 www philips com luminaires Philips Lighting Canada Ltd 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 www philips com luminaires 9140053520 February 2016 ...