4

Room Combine Switch Overview 

Room Combine Switch Overview

The Lytemode Room Combine Switch provides easy partition 
control of meeting rooms, banquet halls, and other large partitioned 
spaces. When partitions are open, the Room Combine Switch links 
the Master Stations in each room so that adjustments to one Master 
Station are duplicated on all linked Master Stations, maintaining a 
uniform look throughout the expanded space. When partitions are 
closed, the Room Combine Switch isolates the Master Stations in 
each room for individual room control.

The Room Combine Switch is capable of controlling up to eight 
partitions. Three Room Combine Switches may be linked together 
for control of up to 24 partitions.

H

C

D

E

F

G

B

A

Lighting Panel

Room Combine

A

B

C

D

E

G

F

North

East

West

South

PF1

PF2

Summary of Contents for ILS-CL-8RES

Page 1: ......

Page 2: ... product or part is found by Philips Controls to have been defective in material or workmanship it will be repaired or replaced as deemed necessary by Philips Controls and the replacement will be returned to you free of charge The original user is solely responsible for any costs associated with removal and re installation of the product and shipping to Philips Controls or its authorized supplier ...

Page 3: ... Setting ILS Network ID 6 Setup 8 Mode 8 ID Address 10 LED Intensity 11 Display Version 12 Operation 13 Setting Combine IDs Method 1 13 Setting Combine IDs Method 2 15 Combine Un combine Rooms 16 Factory Defaults and Troubleshooting 17 Resetting Factory Defaults 17 Troubleshooting 18 Installing Custom Buttons 19 Specifications 20 Accessories 20 ...

Page 4: ...2 Customer Service Customer Service Technical and Sales assistance for Lytemode products are available worldwide Phone 1 800 526 2731 In the United States and Canada 1 214 647 7880 Worldwide ...

Page 5: ...the system provides remote access to scenes Master Raise Lower control Multi room partition control or Master Station Lockout Lytemode Master Stations are easily programmed using the front panel buttons without removing the Master Station from the wall and without the need for a computer Lytemode Master Stations are compatible with both Lightolier Controls Insulated Gate Bipolar Transistor IGBT Di...

Page 6: ...ents to one Master Station are duplicated on all linked Master Stations maintaining a uniform look throughout the expanded space When partitions are closed the Room Combine Switch isolates the Master Stations in each room for individual room control The Room Combine Switch is capable of controlling up to eight partitions Three Room Combine Switches may be linked together for control of up to 24 pa...

Page 7: ...age Ensure that two mounting screws are included Step 2 Connect ILS Network Cable to 9 pin connector at back of Room Combine Switch Step 3 Insert Combine Switch into standard deep rough in box not included Secure with two supplied mounting screws Step 4 Snap faceplate into place 1 WH OR Data 2 OR Data 3 SHIELD 4 WH GN Volts 5 GN Ground 6 WH BL Volts 7 BL Ground 8 WH BR Volts 9 BR Ground 9 Pin Conn...

Page 8: ...are in the range of 1 to 255 An ID of 0 will disable the unit and prevent it from transmitting on the network IDs are typically unique For example an ILS Master will require a unique ID to allow dimmers to track its channel levels However ILS Remotes should be given the same ID as the ILS Master it controls ILS Remotes rely on the fact that they are manually triggered to avoid network collisions w...

Page 9: ... your particular device s in order to set corresponding control IDs Device ID Sub ID Devices ID Remotely Polled Notes Remote 1 255 0 Multiple No 1 Two Button Remote Auto 0 n a No 4 Global Remote 1 255 0 Multiple No 2 Remote Keypad 1 255 0 7 1 Yes 3 Remote I O 1 255 0 7 1 Yes 3 Room Combine 1 255 0 1 Yes 3 Mini Master 1 255 0 7 1 Yes 3 Master 1 255 0 7 1 Yes 3 RS 232 Port Auto 0 n a No 4 Smart Matr...

Page 10: ... 1 Press and hold D and E for 3 seconds A LED will blink rapidly Step 2 Enter Mode by setting G and H buttons as either Off or On as shown in the following table LEDs will blink for any Mode not supported Step 3 Press A to save and exit Mode G H 0 RCGP Remote 1 8 Off Off 1 RCGP Remote 9 16 Off On 2 RCGP Remote 17 24 On Off 3 RCGP Master On On H C D E F G B A H C D E F G B A C D B A Example Mode 3 ...

Page 11: ...s unit will Display and Select partition switches 9 16 The third unit should be set to Mode 2 This unit will Display and Select partition switches 17 24 Mode Function 0 RCGP Remote 1 8 Used to Display and Select Partition Switches 1 8 1 RCGP Remote 9 16 Used to Display and Select Partition Switches 9 16 2 RCGP Remote 17 24 Used to Display and Select Partition Switches 17 24 3 RCGP Master Matches m...

Page 12: ... Off 25 Step 2 Enter three most significant ID bits in F G H Use B C to increment decrement value Step 3 Tap A A LED will blink On 25 and Off 75 Step 4 Enter five least significant ID bits in D E F G H Use B C to increment decrement value Step 5 Press A to save and exit ID Values F 128 most significant ID G 64 most significant ID H 32 most significant ID D 16 least significant ID E 8 least signifi...

Page 13: ...g polled will return a Network Test Response if the transmitted ID matches their own ID If the transmitting device sees a Network Test Response it will double blink its ON A LED This is useful for network testing and to determine if the ID is unique LED Intensity The intensity brightness of the LEDs can be set as follows Step 1 Press and hold D and F for 3 or more seconds C D E F LEDs will display...

Page 14: ...ss and hold G and H for 3 or more seconds The Version is displayed in binary format on B H Step 2 Add up values for each illuminated LED and then add 1 00 Example LEDs F and H are On therefore 04 01 1 00 Version 1 05 8 Button LED Value B 64 C 32 D 16 E 08 F 04 G 02 H 01 H C D E F G B A ...

Page 15: ... programmed switches 1 8 or press button switches 9 16 on a second unit set to Mode 1 or press button switches 9 16 on a third unit set to Mode 2 A will blink ONE time and then delay Step 3 Enter three MSBs most significant bits of first ID on bottom three buttons refer to ID Values on next page Step 4 Press A Top button will now blink TWO times and then delay Step 5 Enter five LSBs least signific...

Page 16: ... buttons refer to ID Values below Step 10 Press A The two ID s have now been entered and saved to the selected button Note When entering IDs the B C buttons will increase decrease the displayed ID by one ID values F 128 most significant ID bit G 64 most significant ID bit H 32 most significant ID bit D 16 least significant ID bit E 8 least significant ID bit F 4 least significant ID bit G 2 least ...

Page 17: ...nk ONE time and then delay Step 3 Walk to first room that is to be programmed into the button and press Master Raise or Master Lower button A will blink THREE times and then delay first ID has been captured Step 4 Walk to second room that is to be programmed into the button and press Master Raise or Master Lower button Unit will exit and save the setting It will then turn On the button just progra...

Page 18: ...er the Room Combine Switch has been programmed rooms can be combined LED On and un combined LED Off by pressing the desired button Note If a button is pressed and the LED blinks and turns back Off then the unit has not been properly programmed ...

Page 19: ... 1 Press and hold A and H for 3 or more seconds All LEDs will start to blink Step 2 While still holding A H buttons also press and hold C After another 3 seconds unit will reset back to its Factory Defaults Factory Defaults are as follows Unit Mode 3 RCGP Master Unit ID 0 Disabled LED intensity 75 All Room Combine Switch ID s set to 0 H C D E F G B A H C D E F G B A ...

Page 20: ... will blink an LED to indicate their reception of this command If a receiving device matches the transmitted ID it will blink all of its LEDs Those devices that are capable of being polled will return a Network Test Response if the transmitted ID matches their own ID If the transmitting device sees a Network Test Response it will double blink its ON A LED To send Network Test Command Step 1 Press ...

Page 21: ...hem in the future use the following procedure for installation To install custom buttons Step 1 At 8 button unit remove faceplate Step 2 Remove 8 button plate by removing two screws Step 3 Remove existing button pad Step 4 Insert custom button pad and re assemble components Available from Lightolier Controls www lolcontrols com PC Board Button Pad 8 Button Plate Screw Faceplate ...

Page 22: ...Brown GR Gray and BL Black Faceplates available in W White AL Almond LA Light Almond I Ivory BR Brown GR Gray and BL Black To order custom engraved keypads and faceplates please visit our website at www lolcontrols com Part Number Description ILSCK8B__ Color Kit for 8 Button Remote Station CE8BES Custom Engraved 8 Button Keypad Membrane COMFP2__ Compli Screwless Faceplate 2 Gang COMFP2CE__ Custom ...

Reviews: