Philips ELI-S-20 Installation Instructions Download Page 3

3

step 4

Join the inverter connector & apply power

>  After installation is complete, join the inverter connector and apply AC power.

>  At this point, power should be connected to both the AC ballast and the backup micro inverter, and the 

Charging  Indicator Light should illuminate indicating the battery is charging.

>   A short-term discharge test may be conducted after the backup micro inverter has been charging for 1 hour. 

Charge for 24 hours before conducting a long-term discharge test. 

refer to operation.

illustration 1

  The T-BAR mounting bracket assembly is sold separately and is available from the factory as an accessory kit (T-BAR-MB).   

Call your local distributor or the factory for complete information.

T-BAR

BRACKET

MICRO INVER

TER

1

2

4

3

4

TEST/MONITOR

PLATE

INSTALLATION

Backup Micro Inverter

No Shading  – Equipment supplied by others

1    –  Flexible conduit (supplied) to connect ballast wires.

2    –  Existing conduit to run existing wires to lamp holder.

3    –  AC line in.

4    –  Conduit and junction box (not supplied).

Summary of Contents for ELI-S-20

Page 1: ...ters 8 This product is for use with indoor or damp locations where ambient temperature is 0 C to 50 C Not suitable for wet or hazardous locations 9 This is a sealed unit Integral battery is not replaceable Replace entire unit when necessary 10 The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition 11 Do not use this product for other than intended use 12 S...

Page 2: ...he AC ballast driver Select a suitable location for the backup micro inverter and install such that its output leads can connect to the input leads of the AC ballast driver See Illustration 1 for typical installation and select appropriate mounting method STEP 1 Disconnect AC power from fixture INSTALLATION 2 Verify that the inverter connector red and white is disconnected Note that the unswitched...

Page 3: ... for 1 hour Charge for 24 hours before conducting a long term discharge test Refer to OPERATION Illustration 1 The T BAR mounting bracket assembly is sold separately and is available from the factory as an accessory kit T BAR MB Call your local distributor or the factory for complete information T BAR BRACKET M I C R O I N V E R T E R 1 2 4 3 4 TEST MONITOR PLATE INSTALLATION Backup Micro Inverter...

Page 4: ... ensure that it is working The following schedule is recommended 1 Visually inspect the charging indicator light monthly It should be illuminated 2 Test the emergency operation of the fixture at 30 day intervals for a minimum of 30 seconds The lamp should operate at full illumination 3 Conduct a 90 minute discharge test once a year The lamp should operate at full illumination for at least 90 minut...