DUS360CR Installation Instructions Rev 02

 Specifications subject to change without notice

Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921)  Unit 6, 691 Gardeners Road  Mascot  NSW  2020  Australia  Tel: +61 2 8338 9899 Fax: +61 2 8338 9333

E-Mail: 

[email protected]

      Web: 

http://philips.com/dynalite

DyNet Terminal

 

5-way pluggable screw terminal

 

1 x 2.5mm

2

 conductor size

DyNet Network Supply

  RS485 12-24 VDC, 20mA max

PIR sensor: 

Quad element pyroelectric

Max detection range

5 m

Detection area: 

7.4 m x 5.6 m (at 2.4m mounting height)

Detection speed: 

1 m/s

Detection object: 

700 mm x 250 mm

Detection zones: 

64

Activation indicator: 

Red LED

PE cell: 

<5 to >5000 lux (reflected)

 

Automatic daylight harvesting mode

Controls:

 

DIP switch (DUS360CR-DA only)

 

Service switch

 

Infrared receiver (supports RC5)

Compliance: 

cULus, CE, RCM, FCC, ICES-003

Operating Conditions: 

Temperature: 0 to 45° C ambient

 

Humidity: 0 to 90% non-condensing

Storage & Transport: 

Temperature: -25 to 70° C ambient

 

Humidity: 0 to 90% non-condensing

Construction: 

Polycarbonate plastic enclosure

Dimensions: 

72 mm dia. x 41 mm (2.8” dia. x 1.6”)

Packed Weight: 

105 g

Installation Steps

1. 

Install the sensor into a 64 mm wide round hole in a firm section of the ceiling. The mounting position should adhere to the following:

• 

Ceiling height should be between 2.1 m and 4.0 m. Optimum height is 2.4 m.

• 

Position the sensor at least 1 m away from electrical lighting such as neon and fluorescent lights.

• 

Avoid exposure to direct sunlight and heating/cooling sources.

• 

Position the sensor where pedestrian traffic is likely to move through the detection zone.

• 

Note that the sensor coverage area is rectangular, approximately 7.6 m x 5.4 m (at 2.4 m installation height).

• 

The detection range above is specified for an ambient temperature of 25ºC. This range is reduced at higher temperatures.

2.  If needed, pull out and rotate the PIR shield to block a 120

º

 viewing angle.

3. 

DUS360CR-DA ONLY: Set the device’s Area, Timeout and Corridor Hold ON feature using the DIP switches as detailed below and on the 

device label. If using Corridor Hold ON feature, enable this option on only one sensor in the designated corridor Area.

4. 

Terminate the DyNet cable as indicated below. If using the dual-socket RJ12 or RJ45 connector, follow the pinout shown.

 

If terminated and powered correctly, the red indicator LED turns on for 5 seconds.

Recommended Cable Type

Dynalite DYNET-STP-CABLE or equivalent 

shielded four twisted-pair cable.
See the DYNET-STP-CABLE datasheet for more 

information.

Green/White Pair

 

Paralleled for GND

Orange/White Pair

 

Paralleled for +V (12-24 VDC)

Blue/White Pair

 

Blue for DATA+

 

White for DATA-

Brown/White Pair

 

Spare

Product Specifications

Daisy chained 

device

First or last device

S

HL

D

G

ND

D+

D-

+V

A

ux

Shield

Green/Green white

Blue

Blue white

Orange/Orange white

Brown/Brown white

S

HL

D

G

ND

D+

D-

+V

A

ux

Recommended Cable Color Coding

5

4

3

2

1

5

4

3

2

1

1

17

2

18

3

19

4

20

5

21

6

22

7

23

8

24

9

25

10

26

11

27

12

28

13

29

14

30

15

31

v

16

(DUS360CR-DA ONLY)

DIP Switch Area Selection Table

Area

+

+

+

GND GND

RJ12 socket

GND

GND

+

+

N/A D 

-

N/A

+

RJ45 socket

On

Off

RS485 DyNet network