DUS360CR Installation Instructions Rev 02
Specifications subject to change without notice
Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921) Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
E-Mail:
Web:
http://philips.com/dynalite
DyNet Terminal
5-way pluggable screw terminal
1 x 2.5mm
2
conductor size
DyNet Network Supply
RS485 12-24 VDC, 20mA max
PIR sensor:
Quad element pyroelectric
Max detection range
:
5 m
Detection area:
7.4 m x 5.6 m (at 2.4m mounting height)
Detection speed:
1 m/s
Detection object:
700 mm x 250 mm
Detection zones:
64
Activation indicator:
Red LED
PE cell:
<5 to >5000 lux (reflected)
Automatic daylight harvesting mode
Controls:
DIP switch (DUS360CR-DA only)
Service switch
Infrared receiver (supports RC5)
Compliance:
cULus, CE, RCM, FCC, ICES-003
Operating Conditions:
Temperature: 0 to 45° C ambient
Humidity: 0 to 90% non-condensing
Storage & Transport:
Temperature: -25 to 70° C ambient
Humidity: 0 to 90% non-condensing
Construction:
Polycarbonate plastic enclosure
Dimensions:
72 mm dia. x 41 mm (2.8” dia. x 1.6”)
Packed Weight:
105 g
Installation Steps
1.
Install the sensor into a 64 mm wide round hole in a firm section of the ceiling. The mounting position should adhere to the following:
•
Ceiling height should be between 2.1 m and 4.0 m. Optimum height is 2.4 m.
•
Position the sensor at least 1 m away from electrical lighting such as neon and fluorescent lights.
•
Avoid exposure to direct sunlight and heating/cooling sources.
•
Position the sensor where pedestrian traffic is likely to move through the detection zone.
•
Note that the sensor coverage area is rectangular, approximately 7.6 m x 5.4 m (at 2.4 m installation height).
•
The detection range above is specified for an ambient temperature of 25ºC. This range is reduced at higher temperatures.
2. If needed, pull out and rotate the PIR shield to block a 120
º
viewing angle.
3.
DUS360CR-DA ONLY: Set the device’s Area, Timeout and Corridor Hold ON feature using the DIP switches as detailed below and on the
device label. If using Corridor Hold ON feature, enable this option on only one sensor in the designated corridor Area.
4.
Terminate the DyNet cable as indicated below. If using the dual-socket RJ12 or RJ45 connector, follow the pinout shown.
If terminated and powered correctly, the red indicator LED turns on for 5 seconds.
Recommended Cable Type
Dynalite DYNET-STP-CABLE or equivalent
shielded four twisted-pair cable.
See the DYNET-STP-CABLE datasheet for more
information.
Green/White Pair
Paralleled for GND
Orange/White Pair
Paralleled for +V (12-24 VDC)
Blue/White Pair
Blue for DATA+
White for DATA-
Brown/White Pair
Spare
Product Specifications
Daisy chained
device
First or last device
S
HL
D
G
ND
D+
D-
+V
A
ux
Shield
Green/Green white
Blue
Blue white
Orange/Orange white
Brown/Brown white
S
HL
D
G
ND
D+
D-
+V
A
ux
Recommended Cable Color Coding
5
4
3
2
1
5
4
3
2
1
1
17
2
18
3
19
4
20
5
21
6
22
7
23
8
24
9
25
10
26
11
27
12
28
13
29
14
30
15
31
v
16
(DUS360CR-DA ONLY)
DIP Switch Area Selection Table
Area
V
+
V
+
D
-
D
+
GND GND
RJ12 socket
GND
GND
V
+
V
+
N/A D
-
N/A
D
+
RJ45 socket
On
Off
RS485 DyNet network