Philips Dynalite DUS360CR Quick Start Manual Download Page 1

DUS360CR / DUS360CR-DA

To reduce the risk of device failure, do not expose this device to rain or moisture. Installation, programming and maintenance must be 

carried out by qualified personnel. All local wiring and electrical regulations must be followed when installing device.

Low profile 360° ceiling sensor

Read Instructions

 – We recommend that you read these 

instructions prior to commencement of installation. 

Check Connections

 – Ensure that all wiring terminals are securely 

connected.

Mounting Location

 – For indoor use only. Select sensor locations 

as per user requirements. Note that the optimal locations for PIR 

and PE use may be different, requiring multiple sensors in the 

same area. This device is suitable for plenum use.

Data Cable

 – Use screened, stranded RS-485 data cable with four 

twisted pairs. Segregate from mains cables by at least 300mm.  

Connect devices in a ‘daisy chain’ configuration. A data cable that 

is connected to an energized device is live. Do not cut or terminate 

live data cables.

Power supply

 – This device must be powered by a certified class 

2 energy limited source for North America, or SELV for EU regions.

Installation

 – Installation must be done in accordance to the local 

wiring code (or wiring rules). Installation of the home and building 

automation and control system shall comply with HD60364-4-

41. The temperature limits and current-carrying capacities of 

the communication wires specified in HD 384.5.523 shall not be 

exceeded. Network Topology for installation is Daisy Chain.

Lens Pattern

Dimensions

Hardware

Light level 

sensor

- Network sign-on button 

- IR receiver 

- Red LED indicator

120º PIR shield

PIR sensor

8m

6m

0

1

2

3

4

1

2

3

4

0

1

1

2

2

3

3

WARNING

This is a SELV (Safety Extra Low Voltage) device and 

must be isolated and segregated from mains and other 

wiring as per the local wiring rules

To reduce the risk of device failure and to avoid damage to the unit, disconnect 

network and device power before installation or servicing. It is recommended that 

an electrician perform this installation.

Do not expose this device to rain or moisture. Connect the cable shield to the 

provided shield termination on the device connection port. If no shield termination 

is provided on the device, connect the cable shield to the equipment grounding 

conductor of the supplying branch circuit(s). Installation, programming and 

maintenance must be carried out by qualified personnel.

72mm

2.8in

63mm

2.5in

41mm

1.6in

39mm

1.5in