background image

 

         

installation steps 

 

        connecting data cable

 

 
 

    

        

product specifications

 

 

 

1.  Decide if the equipment to be connected to the RS232 port 

is classified as COMPUTER (DTE) or MODEM (DCE). The 
factory setting for the RS232 port is Computer. To change 
this setting to MODEM remove the cover and move the 
mode jumpers to the MODEM position. 

2.  Connect the RS232 port on the DNG232 to the RS232 port 

on the other device using a 9 pin D connector straight 
through cable. 

3.  Connect the RS485 cable to the DyNet 5 way terminal strip. 

Note that this device consumes 40mA of power from the 
DyNet network 

4.  The factory settings will allow control of a Dynalite system 

via plain English text strings that can be sent by a terminal 
program such as the one included in Microsoft Windows, 
which allows the DNG232 to be easily tested. See the 
section on Plain English commands. Detailed programming 
information is available in the document: DNG232 
Programming Manual 

RS485 Serial Port: 

1 x RS485 unterminated DyNet, consisting of 1 x RJ12 socket & 1 x 5 way terminal strip, for permanent 

connections 

RS232 Serial Port: 

1 x RS232 9 pin female D connector 

RS232 Port Modes: 

COMPUTER (DTE), MODEM (DCE) 

RS232 Data Formats: 

Baud rate: 1200 - 460800, Max packet length: 254 bytes, Data bits: 7/8, Stop bits: 1/2, Parity: 

odd/even/none 

User Controls: 

Service Switch, Diagnostic LED 

Internal Controls: 

Programmable Logic Controller 

Operating Environment: 

0º to 50ºC ambient temperature, 0% to 95% RH non condensing 

Power Consumption: 

40mA from the DyNet network 

Compliance: 

CE, C-Tick 

Ambient Temperature: 

50

C max. 

Construction: 

ABS plastic stand alone enclosure 

Dimensions: 

H 30mm x W 80mm x D 150mm 

Weight: 

0.15Kg 

 

 
 
 

 

DMNG232 Instruction Manual Rev E.Doc  Specifications subject to change without notice 

Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921)  Unit 6, 691 Gardeners Road  Mascot  NSW  2020  Australia  Tel: +61 2 8338 9899 Fax: +61 2 8338 9333 

E-Mail:  

[email protected]

      Web:  

dynalite-online.com

 

RS232 Connector: 

9 pin Female D connector 

 
RS232 Connector Pinouts 

Pin

 

Function

 

Implementation

 

DCD (data carrier detect) 

Not connected 

RD (received data) 

Connected to UART 

TD (transmitted data) 

Connected to UART 

DTR (data terminal ready) 

Not connected 

SG (signal ground) 

Connected to Ground 

DSR (data set ready) 

Not connected 

RTS (request to send) 

Software controlled 

CTS (clear to send) 

Software controlled 

RI (ring indicator) 

Not connected 

 

connecting RS232 data cable 

Connect Data Cable in a „Daisy Chain‟ 

 

RJ12 Socket Connections 

Serial Cable Permanent Connections 

 

recommended cable colour coding 

Green/White Pair

   

paralleled for GND 

Orange/White Pair 

 

paralleled for +12V 

Blue/White Pair

 

 

Blue for DATA+ 

 

 

 

White for DATA-

 

recommended cable types 

Belden:   

9503 

Garland:   

MCP3S 

Hartland:   

HCK603 

M&M Cable: 

B2003CS

 

 

Dynalite:   

DYNET-STP-CABLE 

M&M cable: 

B9503CS 

Multicables: 

AWME120236209220 

RS Components: 

368-687

 

 

 