1. 

After removing both front covers and the required knockouts for the power supply, networking cable and lighting group 

channels, mount the unit in its desired location. Once secured, the DMC4 unit is ready for the internal modules to be 

mounted.

2. 

Mount the communication module below the high-voltage barrier of the DMC4. Refer to the communications module 

installation instructions for more details before proceeding.

3. 

Mount the DSM4-XX power supply module in the middle of the DMC4. Refer to the power supply module installation 

instructions for more detail before proceeding.

4. 

Mount the control modules in the remaining module spaces. Any control module can be mounted in any location and 

any module location can be left empty, provided the corresponding wiring loom connectors are safely insulated (see 

below). Refer to the control module installation instructions for more details.

5. 

Connect the supplied wiring loom to the DMC4 as shown. Use only the loom supplied with the unit, and do not break or 

modify the loom in any way. Make sure the labels on the loom correspond to the wiring on each module. For modules 

requiring termination, remove the black insulating caps from the loom before terminating to the load and supply 

modules. 

For any module location that is not populated or does not require termination, the corresponding 

insulating caps (or mains-rated isolating electrical terminators) must remain in place on the loom.

 Terminate the 

correctly rated supply to each module but do not energize.

6. 

Check and retighten all terminals. Remove the knockout detail on the front cover as required. Replace the top and 

bottom cover plates, and make sure all screws are tightened securely. Stick the labels provided with the modules on the 

cover plate to indicate which module is installed in each location. If an uncovered knockout is not used, cover it with a 

suitable blanking plate.

7. 

The unit is now ready to be energized. If required, the bottom communication module cover can be removed when 

energized to access the override key matrix.

1

2

6

5

4

3

7

Summary of Contents for DYNALITE DMC4

Page 1: ...fications 8 Internal View 3 Mounting 4 Module mounting 5 DMC4 Installation Instructions Rev 02 Specifications subject to change without notice Dynalite manufactured by WMGD Pty Ltd ABN 33 097 246 921 Unit 6 691 Gardeners Road Mascot NSW 2020 Australia Tel 61 2 8338 9899 Fax 61 2 8338 9333 E Mail support controls philips com Web http philips com dynalite ...

Page 2: ...ecial Programming Once assembled powered and terminated correctly this device will operate in basic mode A new Philips Dynalite user interface on the same network will turn all output lighting channels on from button 1 and off from button 4 allowing testing of network cables and terminations Advanced functions and custom presets can then be configured via the EnvisionProject commissioning software...

Page 3: ...ing point Wall mounting point Communication bus cover Knockouts for load group channels High voltage barrier Data cable entry points Surface mounting sleeve For spare parts please call your nearest Philips Dynalite Customer Service Centre Comms module install location Communication bus connection Control module 3 install location Communication bus connection Control module 4 install location Commu...

Page 4: ...ables are connected it is acceptable to replace the top cover and energize the device as the default factory programming is to have all channels set to full output Use the manual override keypad on the communication module to control individual channels This device should be de energized before terminating the control and data cables Select a suitable location This device is designed for indoor us...

Page 5: ...single phase supply to allow the device to be loaded to its maximum capacity Two earth bars are located in the DMC4 unit in the field wiring space on the right To install the Communication Supply and Control modules Connect the module ribbon cable to its respective plug On the left hand side of the module there are two locating tabs which line up with the DMC4 communication bus cover Slide the tab...

Page 6: ...ied wiring loom to the DMC4 as shown Use only the loom supplied with the unit and do not break or modify the loom in any way Make sure the labels on the loom correspond to the wiring on each module For modules requiring termination remove the black insulating caps from the loom before terminating to the load and supply modules For any module location that is not populated or does not require termi...

Page 7: ...7 DMC4 Installation Instructions Rev 02 Dimensions 830mm 32 7in 445mm 17 5in 106mm 4 2in 340mm 13 4in 740mm 29 1in 370mm 14 6in ...

Page 8: ...digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that inter...

Reviews: