DDRC1220FR-GL Installation Instructions Rev 08 Specifications subject to change without notice
Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921) Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
E-Mail:
Web:
www.philips.com/dynalite
Control Supply:
100-240 V 50/60 Hz single phase at 0.25 A, Over-voltage category III, maximum 4kV surge
Load Outputs:
12 x feed-through outputs at 20 A per channel, maximum total device load 180 A
1 Phase & Neutral, 3 Phase & Neutral Star. Some delta wiring supported.
Switching Device:
Relay 50 A 230 VAC resistive (5000 VA lighting load rated), maximum 500 A (200 uS) inrush current
Supply Terminals:
1 x Phase, 1 x Neutral 1 x Earth, up to 5 mm
2
cable per terminal
Load Terminals:
1 x Phase, 1 x Neutral 1 x Earth, up to 5 mm
2
cable per terminal
User Controls:
Service switch, Diagnostic LED
I/O:
1 x RS485 DyNet serial port
1 x AUX programmable dry contact input
DyNet DC Supply:
120 mA (capacity for approximately six panels)
Presets:
170
Programmable Logic:
8 tasks (most UPAN mnemonics supported)
Operating Conditions:
Temperature: 0 to 50° C ambient, Humidity: 0 to 90% non-condensing
Storage & Transport:
Temperature: -25 to 60° C ambient, Humidity: 0 to 90% non-condensing
Construction:
Polycarbonate DIN-rail enclosure, (12 units wide), IP20, UL940-V0 rated
Dimensions:
93 mm x 215 mm x 64 mm (3.7” x 8.5” x 2.5”)
Weight:
0.76 kg
Certification:
CE, RCM
Recommended Cable Type
Dynalite DYNET-STP-CABLE or equivalent shielded
three twisted-pair.
See datasheet for more information.
Recommended Cable Color Coding
Green/White Pair
Paralleled for GND
Orange/White Pair
Paralleled for +12VDC
Blue/White Pair
Blue for DATA+
White for DATA-
Brown/White Pair
Spare, use for SHIELD on unshielded cables
SH
LD
GN
D
D+
D-
+1
2V
Au
x
Shield
Green/Green white
Blue
Blue white
Orange/Orange white
Brown/Brown white
+VE
+VE
D –
D
+
GND GND
RS485 DyNet network
Product Specifications
Electrical Diagram
Supply:
100-240V
1 Phase
0.25A
E
µP
N L IN OUT
CH1
CH2
CH3
CH4
+VE
D
+
D
-
G
ND
Sh
ie
ld
A
UX
CH5
CH6
CH7
CH8
CH9
CH10 CH11
CH12
DyNet
RS485
2 x RJ12
IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT
Data Cable Connection