INSTALLATION

 

INSTRUCTIONS WALL (BACK) MOUNT

 

Remove stencil door (front) from exit housing. Place screwdriver in slot 

1 on bottom of housing and gently pry door in direction 2. Repeat on 

opposite corner. Door should pop loose. See Fig. 1.

 

It  is  not  necessary  to  remove  back  plate  from  housing  when  wall 

mounting.

 

Route  AC  service  wires  through  the  round  center  knockout  in  back 

plate, mount back plate to outlet box using screws. Use the Box 

pattern knockouts in the back panel as needed to mount to wall box 

and secure unit to the wall. See Fig. 2.

 

Remove snap out chevrons as needed.

 

Make  AC  service  connection  at  this  time.  See  OPERATING 

INSTRUCTIONS.

 

INSTRUCTIONS  BACK  PLATE  REMOVAL 

(DOUBLE FACE ONLY)

 

To remove back plate, place screwdriver in slot 1 on bottom of housing 

and gently pry door in direction 2. Repeat on opposite corner. Door 

should pop loose. See Fig. 1.

 

Snap on EXIT stencil and reassemble exit.

 

INSTRUCTIONS CEILING / END MOUNT

 

Remove  the  two  snap-out  plugs  at  the  desired  location  for  the

 

 

 
 
 

 
 
 
 
 
 

 
 

 

Fig. 1

 

 

 
 
 

 
 

PLUG

 

 

 
 
 

 
 
 
 
 
 

 
 

PLUG

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

Fig. 2

 

NORMAL POWER-UP SEQUENCE

 

 

 
 
 

 
 
 

 
 
 

 
 
 

 
 
 

 

APPLY

 

 

 
 

ALL INDICATOR 

LEDs FLASH 6 

TIMES

 

 

 

EMERGENCY LAMPS 

BRIEFLY ON

 

 

 
 
 

 
 
 
 
 
 

 
 
 

 
 
 

 
 
 

 
 
 

 

 

SELF-TESTING / SELF-DIAGNOSTIC 

The unit will self-test approximately every 
30 days for a minimum of 30 minutes.

 

canopy to fit. See Fig. 2.

 

Route supply wires through the hole in the body for the canopy that is 

labeled “<<INPUT FEED ACCESS”.

 

Thread  wires  through  opening  in  canopy.  Insert  canopy  into  holes  in 

body and snap locking bracket (Fig.3) into place, making sure wires 

are clear.

 

Align the metal adapter plate for mounting direction and mount it to the 

junction box with the input wires out though the center hole.

 

Make AC service connection and push the wires and wire nuts back into 

junction box through the center hole in the metal adapter plate and 

mount  the  canopy/exit-sign  to  the  metal  adapter.  SEE 

OPERATING INSTRUCTIONS

 

Remove the snap-out chevrons in the EXIT panels as needed, replace 

EXIT panel(s)  back  on  to  the  sign  and  proceed  to  POWER-  UP 

SEQUENCE.

 

 

 
 
 
 

Fig. 3

 

 

 
 

LED  STRIP

 

LOCKING  BRACKET

 

 

 
 
 

 

CANOPY

 

 
 

 
 
 

LOCKING 
BRACKET

 

 

BACK 
PANEL

 

 

 

 
 

 

 
 

BATTERY 

PACK

 

 

GREEN STATUS - ON 

Battery Charging

 

 
 

 

BATTERY 

INDICATOR 

Y

 

FLASHING

 

 

 

N

 

 

 

LAMP

 

INDICATOR 

Y

 

FLASHING

 

 

 

N

 

BATTERY  DIAGNOSTIC INDICATOR FLASHING AFTER POWER-UP:

 

1)  Most likely the Battery is not connected. Verify that the Battery is connected to the diagnostic charger 

board.

 

2)  If the Battery is connected, wait for 24 hours to charge the Battery. After 24 hours, if the Battery 

indicator LED is flashing, the Battery is faulty and needs to be replaced.

 

3)  After Battery replacement, the Battery indicator LED will stop flashing within approximately 10 to 20- 

sec.

 

 

 

 

 
 

 

LAMP  DIAGNOSTIC INDICATOR FLASHING AFTER POWER-UP:

 

1)  Verify that the LED strip is connected to the diagnostic charger board.

 

2)  If some or all of the LEDs are off, the LED strip needs to be replaced.

 

 

 
 

OPERATING INSTRUCTIONS

 

 

TRANSFORMER

 

 

CHARGER  BOARD

 

 

 

Fig. 4

 

 

CHARGE 

INDICATOR 
FLASHING

 

 

N

 

 

CHARGER DIAGNOSTIC INDICATOR FLASHING AFTER POWER-UP:

 

1)  Indicates a faulty diagnostic charger board that must be replaced.

 

1.  Connect AC supply wires to transformer leads and push through knockout into outlet or ceiling/surface box. Observe the wire colors.

 

BLACK wire 120 volt AC input.

 

WHITE wire common or neutral for 120 or 277 volts AC input. 

RED wire 277 volt AC input.

 

CAUTION: CAP ALL  UNUSED BLACK  OR RED WIRES TO PREVENT SHORTING OR ELECTRICAL SHOCK.

 

Note: when all wiring connections are made, push wires thru knockout into outlet box.

 

2.  Connect the red and black wire with the 2-pin connector from battery to BATT connector on the diagnostic charger board, if not already 

connected.

 

3.  Connect the red and white wire with the 2-pin connector from transformer to XFMR connector on the diagnostic charger board if not already 

connected..

 

4.  Energize AC power to equipment and check the unit using the POWER-UP SEQUENCE (see next page). Leave AC connected for a 

minimum of 24 hours to charge battery before performing 

normal operation/manual 

tests.

 

 

ALL  3  RED 

I

NDICATORS 

FLASHING

 

 

N

 

 

TO NORMAL 

OPERATION

 

ALL  3 DIAGNOSTIC INDICATORS FLASHING AFTER POWER-UP:

 

1)  Verify that the LED strip and the Battery are connected to the diagnostic charger board.

 

2)  If everything is connected then the Transfer function is faulty and the diagnostic charger board must be 

replaced.

 

 
 

 
 
 

 

 
 

 
 
 
 

 

P/N 717053101

 

20120503

 