background image

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

! IMPORTANT SAFEGUARDS !

WHEN USING ELECTRICAL EQUIPMENT, BASIC

SAFETY PRECAUTIONS SHOULD ALWAYS BE 

FOLLOWED, INCLUDING THE FOLLOWING:

SAVE THESE INSTRUCTIONS

THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY.  

THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.

© Philips Emergency Lighting

A Division of Philips Electronics North America Corporation

236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-854-1630 • www.philips.com/bodine

70100194

Installation Instructions

  1.  To prevent high voltage from being present on red & yellow output leads prior to installation, inverter  
    connector must be open. Do not join inverter connector until installation is complete and AC power is  
    supplied to the emergency ballast.
  2.  This product is for use with one (4') 32 W T8 bipin fluorescent lamp.  

 

 

 

 

  3.  Make sure all connections are in accordance with the National Electrical Code and any local regulations.
  4.  To reduce the risk of electric shock, disconnect both normal and emergency power supplies and  

 

    inverter connector of the emergency ballast before servicing.
  5.  This emergency ballast is for factory or field installation in the ballast channel or on top of fixture.
  6.  This product is for use in indoor fixtures except air handling heated air outlets, and wet, damp, or    
    hazardous locations.
  7.  An unswitched AC power source is required (120 or 277 VAC, 60 Hz).
  8.  Do not install near gas or electric heaters.
  9.  Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field
    replaceable. Contact the manufacturer for information on service.
 10.  The use of accessory equipment not recommended by the manufacturer may cause an unsafe 

   condition.

 11.  Do not use this product for other than intended use.
 12.  Servicing should be performed by qualified service personnel.

 

CAUTION:

 Verify that all replacement lamp types marked on the installed luminaire are also identified as suit-

able for use with this inverter/charger pack.

LP400

Ni - Cd

08/01/13

EMERGENCY LIGHTING EQUIPMENT

Summary of Contents for bodine LP400

Page 1: ...ectrical Code and any local regulations 4 To reduce the risk of electric shock disconnect both normal and emergency power supplies and inverter connector of the emergency ballast before servicing 5 This emergency ballast is for factory or field installation in the ballast channel or on top of fixture 6 This product is for use in indoor fixtures except air handling heated air outlets and wet damp o...

Page 2: ...E EMERGENCY BALLAST NOTE Make sure that the necessary branch circuit wiring is available An unswitched source of power is required The emergency ballast must be fed from the same branch circuit as the AC ballast ILLUSTRATION 1 ILLUSTRATION 2 INSTALLATION UNSWITCHED FIXTURE SWITCHED FIXTURE UNSWITCHED FIXTURE SWITCHED FIXTURE SINGLE POLE DOUBLE POLE OPTION BLACK 120V OR ORANGE 277V BLACK AC BALLAST...

Page 3: ...When power fails the emergency ballast automatically switches to emergency power operating one lamp at reduced illumination This emergency ballast will operate one 4 32 W T8 bipin lamp for a minimum of 90 minutes Although no routine maintenance is required to keep the emergency ballast functional it should be checked periodically to ensure that it is working The following schedule is recommended 1...

Page 4: ...M CHARGING INDICATOR LIGHT TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD EMERGENCY BALLAST LAMP 1 LAMP 2 LAMP 3 LAMP 4 EMERGENCY BLACK WHITE YELLOW YELLOW LINE RED RED BLUE BLUE WHT YELL BLK YELLOW RED AC BALLAST BLUE BLUE INVERTER CONNECTOR RED WHITE ORANGE BLACK WHITE VIOLET BROWN 277 V 120 V COM CHARGING INDICATOR LIGHT TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD EMERGENCY BALLAST LAMP 1 ...