Philip Payne 300SD Quick Start Manual Download Page 3

P3 | 

300SD

LED STATUS INDICATION 

   

Operation

Led Status

Normal mode

Green LED- ON 

Commissioning

Green LED- ON

Function test

Green LED- Fast Flash

Duration test

Green LED- Slow flash

Lamp fault/open circuit/short circuit

Red LED - ON

Battery fault

Red LED - Slow flash

Charge fault/Circuit fault

Red LED - Fast flash

Emergency mode

LED OFF

Identification

Red/Green LED -  Slow flash

IMPORTANT

To prevent lamp damage and false triggering of fault status please note the following :-

-Ensure LED’s are connected correctly to the luminaire prior to applying power.

-Do not interrupt unswitched supply during self-commissioning period.

-Please allow 51 hours for charge, discharge, charge cycle.

   

FAULT RECTIFICATION SEQUENCE

1.Fault Identification

Slow Red Flash =
Battery Fault

Permanent Red =
Lamp Fault

Charge Fault

2. Take Remedial Action

Check Lamp/ Replace Lamp 

Check Battery/ Replace Battery

Check Module/ Replace Module

3. Reset Unit/ Check Status

Switch Luminaire unswitched mains off / on
For Specto-XT use the Specto-XT Programmer to check status of luminaire.

4. Automatic Reset

Philip Payne AutoTest automatically resets the module to confirm rectification of fault. The device then reverts to   
standby mode if the fault has been cleared or returns to fault indication if fault persists.
For Specto-XT use the Specto-XT Programmer to initiate function/duration test. The luminaire will pend the test until 
the battery is sufficiently charged. The test status can be retrieved using the Specto-XT Programmer (please leave at 
least 60 seconds between test initiation and reading status).

   

Summary of Contents for 300SD

Page 1: ... 220 240V AC 50 60Hz 90 Luminaires 300SDDL SPECTO XT SPECTO XT 220 240V AC 50 60Hz 90 Luminaires 300SDXT Central Supply 220 240V AC 50 60Hz 176 264V DC 30 Luminaires 300SDLA Central Supply DALI DALI 220 240V AC 50 60Hz 176 280V DC 30 Luminaires 300SDDA DA IMPORTANT SAFETY Before carrying out any servicing on this luminaire ensure that the mains supply is fully isolated Disconnect luminaire before ...

Page 2: ...attare il nostro reparto tecnico Modifiche I prodotti Philip Payne non devono essere modificati dato che qualsiasi modifica potrebbe rendere il prodotto insicuro e invalidare ogni segno di sicurezza approvazione Philip Payne non accetta nessuna responsabilità per prodotti modificati e per danni causati quale risultato delle modifiche apportate agli stessi SpectoXT MM3 N N N N USL L L L USL DALI DA...

Page 3: ...CTIFICATION SEQUENCE 1 Fault Identification Slow Red Flash Battery Fault Permanent Red Lamp Fault Charge Fault 2 Take Remedial Action Check Lamp Replace Lamp Check Battery Replace Battery Check Module Replace Module 3 Reset Unit Check Status Switch Luminaire unswitched mains off on For Specto XT use the Specto XT Programmer to check status of luminaire 4 Automatic Reset Philip Payne AutoTest autom...

Page 4: ...nal PASSED 10 Funtional FAILED REPLACED BATTERY 11 Funtional PASSED 12 3 Hour Duration PASSED Each month or more frequently if a fault is identi fied we recommend the installation is checked for status of L E D s Corrective action if necessary should be taken and recorded on the above form Follow good practice as laid down in relevant legislation such as BS 5266 TO RESET AFTER A FAULT SWITCH LUMIN...

Page 5: ... water ingress to electronic circuits may cause a fire Please contact our Technical Department for advice Modifications Philip Payne products should not be modified Any modification may render the product unsafe and will invalidate any Safety Approval marks Philip Payne will not accept any responsibility for any modified products or for any damage caused as a result of their modification Monthly a...

Reviews: