5.5 Current Trip (Option "T")
The Current Trip option is over current protection that when activated will shut off the units current flow in
1/2 cycle of line power or less. Its peak current detector will initiate a shutdown sequence the instant any
current exceeds the current trip threshold set by potentiometer P3. The adjustment range is 50% to 200%
of unit rated current when going from fully counter clockwise to fully clockwise. The Current Trip is a
latched trip and requires a manual reset via a normally closed dry contact connected to TB1. Current
transformer is included as standard. This option can be disabled by removing jumper X3 on the option
card. (See illustrations 7.3 or 7.4 for Trip Reset terminal block and jumper location.)