13 |
Page
V2.1
Grounding
•
Properly ground the phase converter according to local electrical code.
•
Connect the ground lug to the branch circuit or service ground conductor.
•
Ground the phase converter with an adequately sized conductor according to
local electrical code.
•
Ground wire recommendations based on solid to semi-rigid stranded copper
wire.
Table 12
– Ground Wire Specifications
Models
Recommended
Circuit Breaker (A)
Wire Range (AWG)
Min
Max
PT007/PTE007
60
10
2
PT010/PTE010
80
8
2
PTE015
125
6
2
PT020/PTE020
150
6
2
PT030
225
4
2
PT040
300
4
2
PT050
400
3
2/0
PT060
500
2
2/0
PT075
600
1
2/0
PTE207
60
8
2
PTE210
80
6
2
PTE215
125
6
2
PTE220
150
6
2
PT407/PTE407
30
10
2
PT410/PTE410
40
10
2
PT415/PTE415
60
10
2
PT420/PTE420
70
8
2
PT430
100
8
2
PT440
150
6
2
PT450
175
6
2
PT460
200
6
2
PT475
250
4
2
PT4100
400
3
2/0
See terminal markings for additional wire size and torque information.