12 |
Page
V2.1
INSTALLATION
Mounting Your New Phase Perfect
Proper installation of the unit
is important to the performance and normal operating life of
the unit. The unit should be installed in a location free from:
•
Corrosive gases or liquids
•
Excessive vibration
•
Airborne metallic particles
Mount the unit to a solid, non-flammable surface capable of bearing the weight using the
mounting brackets provided with the unit. Model weights are found in
Mounting Bracket Installation
For shipping purposes, mounting brackets may be installed upside down, or shipped
separately in a bag. If the mounting brackets are not installed in an upright position,
remove the mounting screws, turn to an upright position, and then fasten the screws tightly.
Proper Ventilation
To maintain air circulation for adequate cooling, minimum clearance around the unit must
be maintained. Allow six inches on each side and top, and at least 18 inches below.
Ensure air intake and exhaust openings are not obstructed. If the unit is mounted in a small
room, cabinet, or building, ensure there is adequate ventilation to provide sufficient cooling.
Service Entrance Equipment
Phase Perfect phase converters are suitable for use as service equipment when the
molded case circuit breaker (MCCB)/disconnect, service ground conductor terminal, and
grounding electrode conductor are factory installed and the converter is labeled “Suitable
for use as Service Equipment.” Consult local electrical code for installation guidance.
Source Branch Circuit Protection
If a circuit breaker is not factory installed, branch circuit protection must be installed in the
circuit sourcing the phase converter. See
for recommended circuit breaker sizing.
Fuses may be used for circuit protection, consult local electrical code for proper sizing.
Installation of a disconnection means within sight of the phase converter is recommended.
Summary of Contents for Phase Perfect PT007
Page 13: ...7 Page V2 1 Dimensional Drawings Figure 4 PT Small Frame Dimensions...
Page 14: ...8 Page V2 1 Figure 5 PT Medium Frame Dimensions...
Page 15: ...9 Page V2 1 Figure 6 PT Large Frame Dimensions...
Page 16: ...10 Page V2 1 Figure 7 PTE Frame 1...
Page 17: ...11 Page V2 1 Figure 8 PTE Frame 2...
Page 46: ...40 Page V2 1 NOTES...