VersiStart i II   

 

 

 
 

1.

 

Caution Statements 

Caution Statements cannot cover every potential cause of equipment damage but can highlight common 

causes of damage.  It is the installer's responsibility to read and understand all instructions in this manual prior 

to installing, operating or maintaining the equipment, to follow good electrical practice including applying 

appropriate personal protective equipment and to seek advice before operating this equipment in a manner 

other than as described in this manual. 

 

 

Isolate the VersiStart i II completely from the power supply before attempting any work on the 

VersiStart i II or motor. 

 

 

Cables to the control inputs must be segregated from mains voltage and motor cabling. 

 

 

Some electronic contactor coils are not suitable for direct switching with PCB mount relays.  Consult 

the contactor manufacturer/supplier to confirm suitability. 

 

 

Do not apply incorrect voltages to the control input terminals. 

 

 

Power factor correction capacitors must be connected to the supply side of the soft starter. Connecting 

static power factor correction to the output side will damage the soft starter.  

 

The examples and diagrams in this manual are included solely for illustrative purposes.  The information 

contained in this manual is subject to change at any time and without prior notice. In no event will responsibility 

or liability be accepted for direct, indirect or consequential damages resulting from the use or application of this 

equipment. 

 

 

WARNING - ELECTRICAL SHOCK HAZARD 

The VersiStart i II contains dangerous voltages when connected to mains voltage. Only a qualified 

electrician should carry out the electrical installation. Improper installation of the motor or the 

VersiStart i II may cause equipment failure, serious injury or death. Follow this manual and local 

electrical safety codes. 

 

 

GROUNDING AND BRANCH CIRCUIT PROTECTION 

It is the responsibility of the user or person installing the VersiStart i II to provide proper grounding and 

branch circuit protection according to local electrical safety codes.  

 

 

SHORT CIRCUIT 

The VersiStart i II is not short circuit proof. After severe overload or short circuit, the operation of the 

VersiStart i II should be fully tested by an authorised service agent.  

 

1.1

 

Avertissements à l'attention des clients canadiens 

 

AVERTISSEMENT   

L'icône AVERTISSEMENT ci-contre signale les informations concernant des risques pouvant 

entraîner des blessures graves, voire mortelles. Pour votre sécurité, veuillez consulter les 

avertissements sur cette page ou demander une copie du présent manuel en français auprès de votre 

distributeur local. 

 

 

AVERTISSEMENT   

Isoler complètement le VersiStart i II de l'alimentation secteur avant de tenter toute intervention sur le 

VersiStart i II ou sur le moteur. Les bornes de commande peuvent être au potentiel de la tension de 

phase. 

 

 

AVERTISSEMENT - DANGER D'ÉLECTROCUTION 

Le VersiStart i II contient des tensions dangereuses lorsqu'il est raccordé à l'alimentation secteur. 

Seul un électricien compétent peut effectuer l'installation électrique. Une mauvaise installation du 

moteur ou du VersiStart i II peut déclencher une panne d'équipement, provoquer de graves blessures 

ou même la mort. Suivre les instructions de ce manuel et des codes locaux concernant la sécurité 

électrique. 

 

 

AVERTISSEMENT 

Toujours appliquer la tension de commande avant (ou en même temps que) la tension secteur. 

Summary of Contents for VersiStart i II

Page 1: ...ion 4 3 1 Dimensions and Weights 4 3 2 Physical Installation 4 4 Electrical Installation 5 4 1 Power Terminations 5 4 2 Control Voltages 5 4 3 Control Circuits 6 4 4 Outputs 7 4 5 Electrical Schematic...

Page 2: ...Only a qualified electrician should carry out the electrical installation Improper installation of the motor or the VersiStart i II may cause equipment failure serious injury or death Follow this manu...

Page 3: ...and 2014 35 EU Low voltage directive is not proved The devices of the VersiStart i II series are electrical equipment that is used in industrial electrical power installations They are designed for a...

Page 4: ...VS i II 170 200 160 240 216 214 114 5 51 6 5 VS i II 200 7 87 6 30 9 44 8 50 8 43 4 5 2 0 14 33 3 2 Physical Installation 1 2 3 4 08241 D VS i II 018 VS i II 100 Allow 100 mm 3 9 inch between soft st...

Page 5: ...428 A 6 mm 0 24 inch Torx T20 3 Nm 2 2 ft lb Torx T20 4 Nm 2 9 ft lb n a n a 7 mm 3 Nm 2 2 ft lb 7 mm 4 Nm 2 9 ft lb n a 3 5 mm 0 5 Nm max 4 4 in lb max 4 2 Control Voltages VersiStart i II soft start...

Page 6: ...trol input terminals 01 02 Two wire control Three wire control 110 240 VAC 24 VAC VDC A3 A1 A2 01 02 A3 A1 A2 01 02 1 1 03241 D A3 A1 A2 01 02 A3 A1 A2 01 02 2 3 2 3 03242 E 380 440 VAC Start stop To...

Page 7: ...shunt trip mechanism of an upstream circuit breaker in order to isolate the motor branch circuit or to signal the trip to an automation system or externally The relay will open when the trip is reset...

Page 8: ...the motor during the soft start Current Time Motor Trip Class 08246 A Select the trip class for motor overload protection The trip class reflects the maximum time in seconds that the motor can run at...

Page 9: ...ed time E Current Time Auxiliary Relay Function 08250 A Select the function of the soft starter s programmable output terminals 23 24 When set to Run the relay will operate when the soft start is comp...

Page 10: ...thermistor connection B4 B5 Allow motor to cool x 5 Current imbalance Check for mains supply or line current imbalance L1 L2 L3 x 6 Supply Frequency Check mains voltage is available and supply freque...

Page 11: ...and low frequency limits both apply with no time delay A supply frequency trip will also occur if all three input phases are lost while the soft starter is running all three input phases fall below 12...

Page 12: ...n Modules VersiStart i II soft starters support network communication via easy to install communications modules Each soft starter can support one communications module at a time Available protocols E...

Page 13: ...0 VAC and 5 6 k 24 VAC VDC Outputs Main contactor relay terminals 13 14 Normally open 6 A 30 VDC 6 A 250 VAC resistive Programmable relay terminals 23 24 Normally open 6 A 30 VDC 6 A 250 VAC resistive...

Page 14: ...ics and distortion IEC61000 2 4 Class 3 EN IEC61800 3 Short Circuit Rated short circuit current VS i II 018 to VS i II 048 5 kA 1 Rated short circuit current VS i II 060 to VS i II 200 10 kA 1 1 These...

Page 15: ...C 50 C VS i II 018 18 A 17 A 17 A 15 A VS i II 034 34 A 32 A 30 A 28 A VS i II 042 42 A 40 A 36 A 33 A VS i II 048 48 A 44 A 40 A 36 A VS i II 060 60 A 55 A 49 A 45 A AC53b 4 6 594 1000 metres AC53b 4...

Page 16: ...URD30xxxA0160 A070URD30xxx0160 170M 1318 160 FEE VS i II 048 15000 6 6URD30xxxA0160 A070URD30xxx0160 170M 1318 180 FM VS i II 060 18000 6 6URD30xxxA0160 A070URD30xxx0160 170M 1319 180 FM VS i II 075 5...