8
VBMS ....
8.
LED indicators
LED - on
Operational status
Fault correction
Illuminated
Motor runs
Flashing 1x repeatedly
with a short pause
no
motor
stillstand
detected
Fault will be reset by motor restart
(voltage on T1, T2, T3).
Flashing 2x repeatedly
with a short pause
Adjusted braking current
was not reached
Flashing 3x repeatedly
with a short pause
Braking frequency too
high
Fault can only be reset by discon-
necting the device for 5s from the
mains voltage (motor contactor is inter-
locked).
Flashing 4x repeatedly
with a short pause
Contacts of the motor
contactor are charred/
short-circuited.
Flashing 5x repeatedly
with a short pause
3x in succession no motor
stillstand detected
Flashing 6x repeatedly
with a short pause
Program error
LED - braking
Operational status
Illuminated
Braking current is flowing
Summary of Contents for 2C000.23020