INSTALLATION INSTRUCTIONS

-05- 

-06-

-04-

TO TEST OCCUPANCY SENSORS

DIP SWITCH SETTING

TROUBLESHOOTING

WARRANTY INFORMATION

The sensors are factory preset to allow for quick installation in most applications. Verification

of proper wiring or coverage, or customizing the sensor's settings can be done using the

following procedures. To make adjustments, open the Front Cover with a small screwdriver.

There is a 40-second warm-up period when power is first applied.

Before making adjustments, make sure the office furniture is installed, lighting circuits are

turned on, and the HVAC systems are in the overridden/on position. VAV systems should be

set to their highest airflow. Set the DIP switches to the desired settings. See “DIP Switch

Setting”.

2. Ensure the Time Delay is set for Test Mode* using the “5 seconds/Autoset” setting.

1. Ensure the PIR Activity is enabled, red LED flashes, Hold ON mode are OFF (DIP 9 switch

OFF) and PIR Sensitivity is set to MAX (DIP switch 1 ON).

(DIP switches 2, 3 & 4 are OFF).

3. Ensure that the Light Level is at default (maximum). See the Light Level Feature section of

this document for instructions.

4. Remain still. The red LED should not flash. The green LED and load are ON, and the lights

should turn off after 5 seconds. (If not, see “Troubleshooting.”)

5. Move about the coverage area. The lights should come on.

When testing and adjustment is complete, reset DIP Switches and Light Level to the desired

settings, and replace the cover on the sensor.

* If you need to invoke the Test Mode and the DIP switches are already set for 5 seconds/

Autoset, toggle DIP switch #3 ON then back to the OFF position. This provides a 5 minute

test period. During the test period, the Time Delay is only 5 seconds.

Sensitivity Setting: Switch 1

50% , sensor's coverage is smaller, just about half of the widest range.

100% , the maximum range of sensor's coverage is 1200 square feet, see "coverage pattern".

The PS-P24-CM has 9 DIP switches under the cover. They are used to set sensitivity,

time delay, walk through mode, vacancy mode, audible, visual alarm and Hold ON  feature settings.

Sensitivity

50%

100%

Walk Through

Disabled

Enabled

Vacancy

Disabled

Enabled

Time Delay

5 Sec/Autoset

30 Seconds

5 Minutes

10 Minutes
15 Minutes
20 Minutes
25 Minutes

30 Minutes

Audible Alert

Disabled

Enabled

Visible Alert

Disabled

Enabled

Hold ON
Disabled

Enabled

1

5

6

7

8

9

2

3

4

=OFF 

=ON 

=Factory Setting

sensor will turn the lights off. The sensor can select the time delay using Autoset, or you can

Time Delay: Switches 2, 3, 4

The sensor will hold the lights on as long as occupancy is detected. The time delay countdown

starts when no motion is detected. After no motion is detected for the length of the time delay, the

select a fixed time delay.

Autoset records occupancy patterns and uses this history to choose an optimal time delay from

5s to 30 minutes. AutoSet behavior starts immediately and is refined continually as history is

collected.

Walk Through Mode: Switch 5

Turns the lights off three minutes after the area is initially occupied, if no motion is detected after

the first 30 seconds. If motion continues beyond the first 30 seconds, the selected time delay

applies. Only when a fixed delay is set greater than or equal to 5-minute the walk mode is effective.

Vacancy Mode: Switch 6

Manual on function is achieved by using a momentary switch. The switch connected to the sensor's

"Manual ON" and  "Common". Each time the switch is pressed, the load will be reverted. The operation

of the sensor connected to manual switch depends on the DIP switch 6 setting.

Vacancy ON: In this mode, press the momentary switch again to turn on the load based on the

occupancy. This effective occupancy holds the load ON. After the time delay ends the manual

switch must be used to turn the load on, if there is no movement detected within the 30 second

period.

Automatic On: This mode, which is Vacancy Feature, uses occupancy to turn the load ON. A

manual switch provides the following additional functionality:

a. The load can be turned ON by manual switch activation and it stays on as long as occupancy is

detected. The sensor time delay operates as programmed. When the load turns OFF due to lack

of occupancy detection, the load can be turned ON again by occupancy detection or switch

activation.

b. Activating the manual switch while the load is ON turns the load OFF.

When the load is turned OFF manually, as long as the sensor continues to detect occupancy the

load stays OFF. Five minutes after the last occupancy detection, the lights stay off and the sensor

reverts to the automatic-on mode.

When the load is turned OFF manually, pressing the switch again turns the load ON and the

sensor reverts to the automatic-on mode.

Once the sensor returns to automatic-on mode, either the switch or occupancy detection can

turn the load ON.

Audible Alert: Switch 7

When this feature is turned on, 1 minute, 30 seconds, or 10 seconds before the time delay expires

you can hear "tick" from the buzzer, indicate that time delay is over.

Visible Alert: Switch 8

When this feature is turned on,1 minute delay before the time delay expires the load will flash

once to remind.

Hold ON: Switch 9

To override all sensor functions, set DIP switch 9 to the ON position. The green LED, red LED will

come on and stay on for the duration of the override.

This bypasses the light level, occupancy detection, and the manual ON functions will be invalid,

only to hold the load ON.

Lights do not turn on with occupancy, and the following condition exists:

PIR Activity LED does not flash:

NOTE: When power is initially applied to the sensor, there is a warm-up period of up to 40 seconds

before the LED is active.

CAUTION!

TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE WORKING

WITH OR NEAR HIGH VOLTAGE.

2. Make sure that the PIR Sensitivity is set for Max/Autoset (DIP switch 1 ON ).

1. Check that the circuit breaker has been turned back on.

3. Check all sensor and power pack wire connections.

4. Check for 24V input to the sensor.

- If 24V is present, replace the sensor.

- If 24V is not present, check that high voltage is present to power pack. If it is, replace

power pack.

PIR Activity LED flashes:

1. If the sensor's Light Level has been turned to “ + ”, the lights connected to the Light Level

Output might be held off because of the level of ambient light in the controlled area. To test

whether the Light Level adjustment is the problem, cover the PIR lens and PIR Activity LED

(see diagram) with your hand to see if the lights turn on. If the lights turn on, the Light Level

setting was keeping the lights off (see, “Sensor Adjustment” for readjustment).

2. Check all sensor and power pack wire connections.

3. Check for 24VDC at the power pack's blue wire connection to sensor while sensor is activated.

If there is no voltage, replace the sensor. If there is voltage, replace the power pack.

Lights do not turn off automatically:

1. The sensor may be experiencing activations from outside the controlled area or from some

type of interference (see ”Unwanted Sensor Activations” below).

2. Check all sensor and power pack wire connections.

3. Disconnect power pack's blue wire:

If the lights do not turn off, replace power pack. Reconnect blue wire.

If the lights turn off, the problem may be in the sensor-to check:

Reconnect the blue wire.

Turn sensitivity and time delay to minimum and allow the sensor to time out.

If the lights turn off, the sensor is working properly (see “Sensor Adjustment” for readjust-

ment of sensor).

Unwanted Sensor Activations (LED flashes):

Possible causes

1. The PIR sensitivity may be set too high.

2. Sensor located too close to HVAC or VAV vents with heavy air flow.

Possible solutions

1. Set DIP switch 1 to OFF and ordering information see if the excess activations stop.

2. Relocate the sensor.

Power pack: 120/277VAC, 50/60Hz, 150mA, 20A ballast or

incandescent, 1HP@120/240VAC

PS-P24-CM

PS-PP3000

PIR Occupancy Sensor, low voltage,

sensor, up to 1200 square feet

Model 

Description

ORDERING INFORMATION

PerfectSense warrants to the original consumer purchaser and not for the benefit of anyone
else that this product at the time of its sale by PerfectSense is free of defects in materials and
workmanship under normal and proper use for five years from the purchase date.
PerfectSense’s only obligation is to correct such defects by repair or replacement, at its
option, if within such five year period the product is returned prepaid, with proof of purchase
date, and a description of the problem to PerfectSense Technologies LLC., Attn: Quality
Assurance Department 7877 College Road Suite #105, Baxter MN 56425. This warranty
excludes and there disclaimed liability for labor for removal of this product or reinstallation.
This warranty is void if this product is installed improperly or in an improper environment,
overloaded, misused, opened, abused, or altered in any manner, or is not used under normal
operating conditions or not in accordance with any labels or instructions. There are no other
or implied warranties of any kind, including merchantability and fitness for a particular
purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of
any such implied warranty, including merchantability and fitness for a particular purpose, is
limited to five years. PerfectSense is not liable for incidental, indirect, special, or
consequential damages, including without limitation, damage to, or loss of use of, any
equipment, lost sales or profits or delay or failure to perform this warranty obligation. The
remedies provided herein are the exclusive remedies under this warranty, whether based on
contract, tort or otherwise.