7
OPERATING INSTRUCTIONS
Airflow direction control
Adjust the air flow direction properly, otherwise, it
may cause discomfort or cause uneven room
temperatures.
Adjust the horizontal louver using the remote
control.
Adjust the vertical louver manually.
To set the vertical air flow (Up--Down) direction
Perform this function while the unit is in operation.
Use the remote control to adjust the air flow
direction. The horizontal louver can be moved at
O
a range of 6 for each press, or swing up and down
automatically. Please refer to the “REMOTE
CONTROL OPERATION MANUAL” for details.
To set the horizontal air flow direction (left - right)
Move the vertical louver manually to adjust the air flow
in the direction you prefer.
IMPORTANT: Before adjusting the vertical louvers, the
supply power must be disconnected.
For some models, the vertical louver can be adjusted
by using the remote control. Please refer to the
“REMOTE CONTROL OPERATION MANUAL”
for details.
Do not operate the air conditioner for long periods with
the air flow direction set downward in cooling or
dehumidifying mode. Otherwise, condensation may
occur on the surface of the horizontal louver causing
moisture to drop on to the floor or on furnishings.
Do not move the horizontal louver manually unless it is
necessary. Always use the remote control.
When the air conditioner is started immediately after it
was stopped, the horizontal louver might not move for
approximately 10 seconds.
Open angle of the horizontal louver should not be set
too small, as COOLING or HEATING performance may
be impaired due to too restricted air flow area.
Do not operate unit with horizontal louver in closed
position.
When the air conditioner is connected to power (initial
power), the horizontal louver may generate a sound for
10 seconds, this is a normal operation.
CAUTION
Range
Range
Vertical
louver
Summary of Contents for 1PAMSH30-SZO-14.5
Page 15: ......
Page 16: ...2020331A2042...