Pereko Q-per 12 Operation And Maintenance Manual Download Page 13

13

Page

Operation and maintenance manual for the Q-PER series boilers with feeders. The producer reserves the right to introduce technical modifications.

4.3.  Boiler ignition

1.  Switch  on  the  controller  (see:  Boiler  controller  operation 

manual) and activate manual work mode,

2.  Check  operation  of  individual  devices:  fan,  feeder,  central 

heating pump activation,

3.  Fill the hopper with a proper fuel and close tightly,
4.  Switch on the fan. The feeder starts to supply fuel for approx. 

2-3 minutes in manual mode. Wait until the fuel appears on 
the cast-iron burner grate.

5.  Ignite fuel using wood chips placed manually on the grate.
6.  After ignition, set proper parameters on the controller (boiler 

operation  temperature,  feeding  time,  feeding  pause  time 
and blow-in force), according to the values speci

fi

ed in the 

controller and feeder operation manual.

CAUTION! Burner door must be tightly closed in the auto-
matic boiler operation mode.
CAUTION!  Do  not  set  boiler  temperature  above  57°C! 
It  increases  the  possibility  of  “dew  point”  appearance, 
which accelerates low-temperature corrosion of the heat 
exchanger. Maintaining water supply temperature below 
57°C  when  using  inappropriate  solid  fuel  types  leads  to 
intensi

fi

ed boiler wear and lowers the its e

ffi

ciency.

After boiler ignition, entire control of the combustion process 

is taken by the controller (see. Controller instruction manual) 
that maintains the set water temperature in the boiler with ref-
erence to the heat demand of the building.

4.4.  Approximate parameters of the controller

The  controller  is  pre-con

fi

gured,  but  its  input  parameters 

change depending on the fuel used and may require individual 
adjustment. Any adjustments shall be made depending on the 
heat demand, type and quality (calori

fi

c value) of coal, or de-

pending on the size of the heating system.

Setting appropriate parameters ensures economic fuel con-

sumption. The adjustment consists in setting the feeding pause 
proper for the heat demand. If the boiler does not reach the set 
temperature, the feeding pause must be gradually shortened, 

increasing the blow-in force. In the opposite situation, when the 
boiler reaches the set temperature easily or starts to discharge 
unburnt fuel, the feeding pause must be extended to provide 
more time for fuel combustion, and the blow-in force must be 
reduced accordingly. The blow-in force shall be adjusted based 
on 

fl

ame  observation.  Properly  adjusted  blow-in  force  gives 

bright-yellow 

fl

ame. Too weak blow-in force results in red 

fl

ame 

and occurrence of black smoke. Excessive blow-in force results 
in short white 

fl

ame.

Recommended boiler start-up settings

Boiler power [kW]

Feeder settings

Fan e

ffi

ciency setting  

Max/Min[%]

Feeder standstill time [s]

Fuel feeding time [s]

8

75

10

60 / 10

12

60

10

80 / 10

18

60

15

80 / 10

24

50

15

80 / 10

Summary of Contents for Q-per 12

Page 1: ...Operation and maintenance manual for the boilers with feeder Q Per...

Page 2: ...rameters of the controller 13 4 5 Fuel refilling 14 4 6 Boiler stopping 14 4 7 Cleaning and maintenance 14 4 8 Emergency stopping of the boiler 15 5 BOILER OPERATION DISTURBANCES BEFORE CALLINGTHE SER...

Page 3: ...ciency of the boiler ensure continuous access to the equipment avoid exceeding water temperature in boiler over 95 C maintain operating pressure not exceeding 2 bar NOTE Boiler installation in accorda...

Page 4: ...n of pressurised equipment oper atingathighertemperatures Heatexchangerpanelsarewelded while the unit casing is reinforced with brackets Location of convection ducts allows cleaning using the upper do...

Page 5: ...aust flue is an integral part of the boiler extracting exhaust gas towards the flue duct 2 3 9 Exhaust gas swirlers Exhaustgasswirlersareinstalledinconvectionductstoswirlthe exhaustgasstream whichincr...

Page 6: ...gas at nominal power C 160 150 Temp of flue gas at minimum power C 70 80 Flue gas mass flow at nominal power g s 5 93 8 42 11 62 16 14 Flue gas mass flow at minimum power g s 1 83 3 29 4 54 8 81 Fuel...

Page 7: ...tmaximum1movertheflooringornotlowerthan 200 cm2 for boilers with power up to 25 kW or 400 cm2 for boilers over 25 kW 2 separate air exhaust duct on the internal wall with cross sectionnotlowerthan140...

Page 8: ...recommended to use the connection at a straight angle because it will cause a loss in the chimney draught Fluewithchimneyshouldbejoinedwithaconnec tor made of steel sheet of thickness 3 mm to be purc...

Page 9: ...reserves the right to introduce technical modifications Equalizing tank Non return ball valve Non return valve Central heating pump Pump Boiler Heaters Storage type water heater for domestic hot water...

Page 10: ...thecentralheatingdesignmustbefollowed Asam ple scheme of boiler connection with the central heating and domestic hot water systems in an open heating system with gravitational or forced water circuit...

Page 11: ...t and is synonymous with loss of the warranty Thesystemcanberefilledwithwateronlywhentheboileris cold Firing up should be restarted after filling the system 3 6 3 Draining water from the system It is...

Page 12: ...pera tures resulting in risk of burn injuries Do not stay on the side of the boiler during the opening of the doors and pay attention to flames Take care of cleanness in the boiler room ensure proper...

Page 13: ...hecombustionprocess is taken by the controller see Controller instruction manual that maintains the set water temperature in the boiler with ref erence to the heat demand of the building 4 4 Approxima...

Page 14: ...utton then scrape the heat to the ash pan using the hook supplied along with the boiler 4 7 Cleaning and maintenance Keepingtheboilercleanisnecessaryforitsreliableandfaultless operation Even a thin la...

Page 15: ...rbancesinboileroperation and methods of dealing with them Symptom Cause Repair Smoking outwards insufficient chimney draught remove leaks in chimney flue or boiler doors insufficient chimney height li...

Page 16: ...onths and 24 months for the components 6 Warranty for tightness of welding joints is not synonymous with warranty for tightness of the whole boiler and is appli cable in case of leaks only on welding...

Page 17: ...ompatible with PN 91 B 02413 2 Incorrect connection in closed system acc to the Journal of Laws of 2009 no 56 item 461 3 Incorrect transport and storage of the boiler 4 Starting the boiler without suf...

Page 18: ...18 Page Operation and maintenance manual for the Q PER series boilers with feeders The producer reserves the right to introduce technical modifications SERVICE ASSISTANCE Date Comments Signature...

Page 19: ...is provided for 10 years 60 months for tightness of the heat exchanger and 24 months for the other components The beginning of the warranty period for the PEREKO boiler is the date of purchase confir...

Page 20: ...ducer Envo sp z o o 27 200 Starachowice ul Radomska 76 POLAND www grupaenvo pl Technical support tel 48 41 274 53 53 fax 48 41 274 53 26 e mail serwis pereko pl mobile 48 602 315 512 604 953 459 660 7...

Reviews: